Advertisement

Error code
Cause
Tempera-
ture of the
02F
circuit board
is too high
No mains
voltage
04F
supply
(two-way
switch only)
06F
No com-
or
munication
between
flashing
remote
control and
fireplace
25
Solution
1.
Turn off the fireplace for approximately 30 minutes.
2.
Then turn on the fireplace.
3.
In case the error reappears, there is insufficient
ventilation in the chamber of the fireplace.
Supply mains voltage.
In case the light on the automatic burner relay
in the technical unit) does not flash:
1.
Check power supply on the mains (230VAC).
2.
If this is correct, check/replace the VDC transformer
and/or automatic burner relay.
In case the light on the automatic burner relay
(in the technical unit) flashes:
1.
Place the remote control as close to the fireplace as
possible.
2. Briefly press
3. Check the transmission strength. See: Checking
transmission strength page 16. Carry out the
following steps to check the transmission strength
between the fireplace and the remote control.
4. Check for objects that could jam the signal
(for instance metal casings).
5. In case the signal keeps flashing -> synchronise.
and wait approximately 60 seconds.