4.6 Legacy Mode
Registers
NOTE
For models EMX4x-0064B and smaller (soft starter model ID 1~4), the current
reported via communications registers is 10 times greater than the actual
value.
NOTE
Legacy Mode reports read-only status information in registers 40003 onwards,
to match the register definitions of the clip-on Modbus Module. Identical data is
also available via registers 30003 onwards.
Register
Description
Reserved
40001
40002
Command
(single write)
40003
Starter state
Reserved
40004
40005
Motor current
Modbus RTU Card (710-16499-00B)
Bits
Details
0 to 2
To send a command to the starter, write the
required value:
1 = Start
2 = Stop
3 = Reset
4 = Quick stop (coast to stop)
5 = Forced communication trip
6 = Start using Parameter Set 1
7 = Start using Parameter Set 2
Reserved
3 to 15
0 to 3
1 = Ready
2 = Starting
3 = Running
4 = Stopping (including braking)
5 = Restart delay (including temperature check)
6 = Tripped
7 = Programming mode
8 = Jog forward
9 = Jog reverse
4
1 = Positive phase sequence (only valid if
bit 6 = 1)
5
1 = Current exceeds FLC
6
0 = Unintialised
1 = Initialised
Reserved
7 to 15
0 to 7
Average 3-phase motor current (A)
Reserved
8 to 15