Basic Parameter Setting - ABB ITS2.1 User Manual

Table of Contents

Advertisement

3

BASIC PARAMETER SETTING

Connect the ITS2.1 via Ekip T&P unit to your computer and start the Ekip Connect software.
Click on the 'SCAN' button in the T&P section of the 'CONNECT WITH YOUR DEVICE' area, the ITS2.1 unit will be
detected and then click the 'Classic view'.
Since the ITS2.1 unit is powered by the Ekip T&P unit, configuration of the ITS2.1 unit can be carried out without
having it fitted into the switch.
The following parameters must be set for the ITS2.1 unit:
1.
Select «Switch type» according to the actual switch type, five basic switches Slimline XR, InlineII, OS,
OT or Other can be selected, each switch type has several different current sizes, make sure your
switch type and rated current are all correct.
2. Set «Nominal Line Voltage» according to the system voltage. If the line voltage in the system is 400 V,
the Nominal Line Voltage should be set equal, if not correctly set, the Fuse monitoring will not work.
3. Depending on the feeding direction of the Slimline XRG or InlineII ZHBM switch, Busbar or terminal
supply, Power direction must be set accordingly.
Note: For standalone ITS, mount the voltage sensing cable on the outgoing side of the switch.
ITS2.1 User Manual rev.04/1SEP622750P0001