15 TROUBLE SHOOTING

Fault Description
Detected current value cannot
match to actual current
Slimline/OTM/OSM cannot be
controlled to open/close by ITS
Fuse blown function cannot work
No voltage data showed
ITS2.1 User Manual rev.04/1SEP622750P0001
Fault Analysis
Switch rated current may not be set
correctly
Switch type may be set as InlineII but
InlineII has no motor
This function wasn't enabled
Nominal line voltage wasn't set correctly
Feeding direction wasn't set correctly on
switch
Trouble shooting method
Check rated current setting on Ekip connect
Main page and correct it on ITS2
configuration page
Check switch type setting on Ekip connect
Main page and correct it on ITS2
configuration page
Check Fuse blown handling setting on Ekip
connect Main page and correct it on ITS2
configuration page
Check nominal line voltage setting on Ekip
connect Main page and correct it on ITS2
configuration page
Check the feeding direction setting
according to Section 9