10.2

InlineII ZHBM power direction setting

For InlineII ZHBM, the power direction setting is done by connecting a jumper to the outlet on ITS adapter
PCBA. When connect to KM6, Busbar Feed is set, when connect to KM5, Terminal Feed is set.
By default the jumper is connected to KM6, so the default mode is Busbar Feed.
Note: Make sure the feeding side setting in Ekip connect aligns to the power direction setting on Inline.
ITS2.1 User Manual rev.04/1SEP622750P0001
ZHBM can be fed from the busbar side (busbar
feed) or from the cable terminal side (terminal
feed)
By default the jumper is connected to KM6 and
the corresponding feeding side in Ekip connect
is BUSBAR SIDE.
31