Standalone Its; Its2.1 Overview - ABB ITS2.1 User Manual

Table of Contents

Advertisement

1.6

Standalone ITS

1.7

ITS2.1 Overview

TEST/Prg
The TEST/Prg is for use of configuration tool
Ekip Connect.
Important: This is NOT an ordinary USB connection,
always use the T&P test and program unit when
connecting a laptop to the ITS2.1 unit
Power LED
The power LED can be configured in two ways:
-
Power indication with a steady light
-
Alive indication with a flash rate of ½ Hz.
When configuring the light is in WINK LED mode (2Hz).
Communication LED
The communication LED indicates as follows:
-
Dark : No valid message received
-
Flashing : Valid message with wrong address
-
Lit : Communication OK
If requests from master ends, the LED will go dark after
30 s.
ITS2.1 User Manual rev.04/1SEP622750P0001
Refer the installation instruction for ITS2.1 Standalone.
Fuse Blown LED
Fuse Blown LED indicates as follows:
-
Dark : All fuses are OK
-
Lit : One or more fuses are blown
-
Flashing :
Nominal line voltage is not set (½ Hz)
Switch opened by motor operation when fuse blown
(2 Hz)
Local/Remote indicator LED and pushbutton
Local/Remote LED indicates as follows (2):
-
Dark : Local mode, commands or setting of
parameters are refused
-
Lit : Remote mode, commands or setting of
parameters are accepted
The push button (Rem) selects mode.