3.4

Installing the flowmeter sensor and pipe components

The installation is described using the example of a pipe component. The description
analogously also applies to the installation using a weld-on adapter.
Fig. 3:
1 Flowmeter sensor
2 Centering pin, outflow side
The flow direction must correspond to the arrow indicated on the pipe component.
The gaskets used must not alter the cross- section of the opening in the pipeline and must
ensure complete tightness once the flowmeter sensor and pipe component have been
installed.
The centering pin on the pipe component or weld-on adapter must be located on the outlet
side downstream of the measuring point.
Check the supplied gasket G according to DIN 11851 between the transducer and the pipe
component / weld-on adapter for signs of damage prior to installation.
When using flange-type pipe components all flange screws must be installed properly.
Connecting threads are to be connected with the pipelines of the system using suitable
sealant. All screw connections are to be checked for tightness.
42/14-37-EN
Schematic representation of the pipe component with external thread
Sensyflow FMT200-D
1
2
3
G01035
3 Pipe component
Mounting
15