Programming
Direct
Parameter Path
Access
F411
Program
Motor
Settings
F412
Program
Motor
Settings
F413
Program
Motor
Settings
F014
Program
Fundamental
Parameters
Frequency Setting
F400
Program
Motor
Motor Model
F115
Program
Terminal
Terminals
F420
Program
Torque
Parameters
Torque Control
F214
Program
Torque
Parameters
Setpoints
F425
Program
Torque
Speed Limiting
F426
Program
Torque
Speed Limiting
F427
Program
Torque
Speed Limiting
F428
Program
Torque
Speed Limiting
Start and run the motor in speed control mode to verify operation. Reduce speed to zero Hertz. If
you are using the demo terminals strip, close switch S1. Otherwise, you will need to make a dry
contact between S1 and CC. This will put the drive into torque control mode.
For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192
efesotomasyon.com -Toshiba inverter,drive,servo,plc
Parameter Name
Parameters
Motor
Number of Motor Poles
Parameters
Motor
Rated Capacity of Motor
Parameters
Motor
Motor Type
V/f Pattern
Parameters
Vector
Autotune
Selection
Input
S1 (or other discrete input
terminal)
Setting
Torque
Selection
Setting
RR
Setting
Torque
Forward
Selection
Setting
Torque
Forward
Level
Setting
Torque
Reverse
Selection
Setting
Torque
Forward
Level
Comments
Configure the number of motor poles to
match that of the motor used
Rated capacity of the motor is kW.
determine kW if Hp is known, multiply Hp
by 0.745
If motor used is not listed as a possible
selection, use 'Other'. and perform autotune
as last step.
Select either 'Sensorless Vector Control
(speed)' or 'Sensorless Vector Control
(speed/torque switching)'
Select 'Reset Motor Defaults'. The G7 will
then apply the correct motor model.
Select #56: Control Switch (torque,postion)
Command
Set to source of torque command. RR used
is this example
Scale RR input as required.
Speed
Limit
Select 'SETTING'
Speed
Limit
Set to desired maximum output frequency in
forward direction while in torque control
mode
Speed
Limit
Select 'SETTING'
Speed
Limit
Set to desired maximum output frequency in
reverse direction while in torque control
mode