Toshiba G7 Series Applications Workbook page 42

Hide thumbs Also See for G7 Series:

Advertisement

Programming
Direct
Parameter Path
Access
F015
Program
Fundamental
Parameters
Frequency Setting
F411
Program
Motor
Settings
F412
Program
Motor
Settings
F413
Program
Motor
Settings
F400
Program
Motor
Motor Model
F367
Program
Feedback
Settings
F368
Program
Feedback
Settings
F702
Program
Utility Parameters
Units
FXXX
Program
Special Control Parameters
Frequency Control
(32) Place G7 in local control mode.
(33) Using the EOI, give the G7 a 1Hz frequency set point.
(34) Press Run.
(35) If output frequency does not reach 1.0Hz, or the display indicates OT or OC, press stop. Possible problems are, direction of
rotation, encoder parameters, motor parameters, and encoder wiring. Please verify motor direction of rotation and the parameters
configured in the programming section.
(36) Increase the frequency setpoint to 60.0 Hz.
(37) Test system under varying load conditions.
(38) If response is slow, or appears to be unstable, contact Toshiba for assistance.
For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192
efesotomasyon.com -Toshiba inverter,drive,servo,plc
Parameter Name
V/f Pattern
Parameters
Motor
Number of Motor Poles
Parameters
Motor
Rated Capacity of Motor
Parameters
Motor
Motor Type
Parameters
Vector
Autotune
Parameters
PG
Number
Pulses
Parameters
PG
PG Input Phases
Display
Frequency
Resolution
Start-up frequency
Comments
Select either PGFeedback Vector Control
(speed/torque)
Control (speed/position)
Configure the number of motor poles to
match that of the motor used
Rated capacity of the motor is kW.
determine kW if Hp is known, multiply Hp
by 0.745
If motor used is not listed as a possible
selection, use Other and perform autotune as
last step
Select Reset Motor Defaults. The G7 will
then apply the correct motor model
of
PG
Input
1024 (set to match PPR of encoder)
2 (use 1 if using non directional encoder)
Display
Change to 0.01
Set to 0.00 to allow the G7 and motor to
produce holding torque at zero speed
or
PGFeedback
Vector
To
42