Programming
Direct
Parameter Path
Access
F115
Program
Terminal Selection
Parameters
F116
Program
Terminal Selection
Parameters
F117
Program
Terminal Selection
Parameters
F004
Program
Fundamental
Parameters
(9) Place G7 in remote control mode
(10) Close F to CC terminal
(11) Close S1 to CC terminal
(12) The drive will ramp up speed until either the S1 contact is opened or upper limit is reached
(13) Close S2 to CC terminal
(14) The drive will ramp down speed until either the S2 contact is opened or lower limit is reached
(15) Close S3 to CC terminal
(16) The drive will ramp down to zero and the frequency setting will be zero
For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192
efesotomasyon.com -Toshiba inverter,drive,servo,plc
Input Terminal Function
Input Terminal Function
Input Terminal Function
Standard Mode Selection
Parameter Name
S1
S2
S3
Frequency Mode #1
Comments
Set S1 function to 44 as when S1 is closed to
CC, the drive will increase the frequency
until the contact is opened
Set S2 function to 45 as when S2 is closed to
CC, the drive will decrease the frequency
until the contact is opened
Set S3 function to 46 as when S3 is closed to
CC, the drive will clear the frequency setting
and stop
Set to Use Motorized Pot Simulation
20