1MRS758405 C
4.3.5
SMU615
Installation Manual
The allowed range for the fixing screws' tightening torque is
0.7...1 Nm.
5.
Install the plug-in unit into the case.
B
C
D
1
2
GUID-51DB3F34-24F2-4889-B417-9F0BD762BB7E V1 EN
Figure 15:
Merging unit semi-flush mounted inclined
A
25 °
1 M4 screws
B
221 mm 2 Gasket
C 9 mm
3 Angled frame
D 107 mm 4 Case
E
133 mm 5 Plug-in unit
F
230 mm
G 190 mm
Rack mounting merging unit
A mounting kit is needed for rack mounting the merging unit. In addition to the
detailed mounting instructions, the 19" rack mounting kit includes:
•
Mounting panel; the type of the mounting panel depends on the number of
mounted devices
•
Screws
1.
Mount the mounting panel to a 19" rack.
2.
Loosen the four M5 fixing screws in the case to fit the case into the panel cut-out.
3.
Mount the case to the panel cut-out.
A
F
E
3
4
5
Section 4
Mounting
G
25