1MRS758405 C
Section 5
5.1
5.2
SMU615
Installation Manual
Connecting

Required tools

Only use a screwdriver and insert bits for Phillips (PH 1) cross-recessed head screws
(M3.5) when handling CT/VT terminals (X120) of screw-compression type.
A
A071178 V2 EN
Figure 27:
Screwdriver for CT/VT terminals of screw-compression type
A Max. ∅5.5 mm
B Max. ∅5 mm
A
A071180 V2 EN
Figure 28:
Insert bits for CT/VT terminals of screw-compression type
A Min. 15 mm

Connecting wires

All connections are made on the rear of the case. No soldering is needed.
Open the screw-compression type terminals before inserting any wires. By
default the terminals are closed at the time of delivery.
Use fine wire in door mounting.