Alarm Assignment Of The Relays - Bender ISOMETER isoRW425 Manual

Insulation monitoring device for unearthed it ac-, ac/dc and dc systems (it systems) for railway applications up to 3(n)ac, ac/dc 440 v
Hide thumbs Also See for ISOMETER isoRW425:
Table of Contents

Advertisement

Modbus register assignment of the ISOMETER®

7.1.3 Alarm assignment of the relays

Several alarms can be assigned to each relay. For the assignment of each relay, a 16-bit-register is
used with the bits described below. The following table applies to relay 1 and relay 2, in which „x"
stands for the relay number. A set bit activates the specified function.
Bit
Display indication
0
Reserved
1
rx
2
+R1 < Ω
rx
3
-R1 < Ω
rx
4
+R2 < Ω
rx
5
-R2 < Ω
rx
6
Z1 < Ω
rx
7
Z2 < Ω
rx
8
U < V
rx
9
U > V
rx
10
test
rx
11
S.AL
12
Reserved
13
Reserved
14
Reserved
15
Reserved
38
isoRW425_D00052_05_M_XXEN / 04.2021
When reading, always 0
When writing, any value
Device error E.xx
x Err
Pre-alarm R1
Fault R
at L1/+
F
Pre-alarm R1
Fault R
at L2/-
F
Alarm R2
Fault R
at L1/+
F
Alarm R2
Fault R
at L2/-
F
Pre-alarm Z1
Alarm Z2
Alarm message U
Undervoltage
Alarm message U
Overvoltage
Manually started self test
Device start with alarm
When reading, always 0
When writing, any value
When reading, always 0
When writing, any value
When reading, always 0
When writing, any value
When reading, always 0
When writing, any value
Meaning