Modubs Exception Codes - Siemens SENTRON PAC3200T Product Manual

7km power monitoring device
Hide thumbs Also See for SENTRON PAC3200T:
Table of Contents

Advertisement

Appendix
A.1 Modbus TCP
A.1.2
Modbus exception codes
Overview
Table A- 2
Exception codes
01
02
03
04
F0
72
Modbus exception codes
Name
Meaning
Illegal Function Illegal function:
Illegal Data
Illegal data address
Address
This address is not permissible for
the slave. This is the case, for
example, if the combination of start
offset and transfer length is invalid.
Illegal Data
Illegal data value:
Value
The request contains a data value
that is not permissible for the slave.
This indicates an error in the re-
maining structure of a complex
request, e.g. an incorrect data
length.
Slave Device
Error in processing the data:
Failure
An indefinite error occurred when
the slave attempted to execute the
requested action.
Write Protec-
The action has been rejected be-
tion ON
cause the write protection is set.
The function code in the re-
quest is not a permissible ac-
tion for the slave.
The slave is in a status in which
it cannot process a request of
this type. This is the case, for
example, if it has not yet been
configured and is requested to
return register values.
Equipment Manual, 02/2020, L1V30415168B-02
Remedy
Check which function
codes are supported.
Check the offset and the
number of registers.
Check that the specified
offset and the specified
data length in the com-
mand are correct.
Check that the specified
offset and the specified
data length are correct.
Deactivate write protection.
PAC3200T

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents