Advertisement

Commissioning
6.3 Parameterizing the device
Selection
Range
Output pulse
Range: 1; 10; 100; 1000
divider
(only for: ener-
gy pulse)
Pulse duration
Duration of the energy pulses
(only for: ener-
gy pulse)
Range: 30 ms to 500 ms
Output remote
Switches the output on expiry of the set time, if the output is no longer addressed.
timeout
(only for: re-
Range: 1 s to 18000 s
mote con-
trolled)
Group assign-
Digital outputs of networked devices can be grouped together to form a switching
ment
group or various switching groups. This enables multiple digital outputs, which may be
(only for: re-
distributed over multiple power monitoring devices, to switch simultaneously.
mote con-
This parameter shows the "switching group" on the bus to which the digital output is
trolled)
assigned.
Range: 1 to 99
"Power demand" parameter
The "power demand" parameter permits the following device settings:
Selection
Range
Time period
The time period records the duration of the period in minutes.
Range: 1 min to 60 min
Synchroniza-
Setting of the synchronization mode:
tion mode
No synchronization:
Switches "Synchronization via Bus" off. Synchronization only takes place after
time set internally in device.
Synchronization via Bus:
Activates "Synchronization via Bus". Deactivates "Synchronization via Digital In-
put".
Synchronization via Digital Input:
Activates "Synchronization via Digital Input". Switches "Synchronization via bus"
off.
56
Factory setting
1
1
Equipment Manual, 02/2020, L1V30415168B-02
Factory setting
1
100 ms
0 s
0