Description

2.1

Features

The PAC3200T is a measuring device for measuring the basic electrical variables in low-
voltage power distribution. The device is capable of single-phase, two-phase, or three-phase
measurement and can be used in three- or four-wire TN, TT and IT networks.
The PAC3200T is mounted on a DIN rail.
Thanks to its large measuring voltage range, the PAC3200T measuring device can be
connected directly in any low-voltage system up to a rated voltage UL-L 480 V. X / 1 A and
x / 5 A current transformers can be used for current measuring. The integrated Ethernet
interface can be used for communication.
Measurement
● Measurement of all relevant electrical variables in an AC system
● Acquisition of the minimum and maximum values of all measured variables
● Averaging of all measured values directly on the device in two steps, which are
independent of each other and freely configurable (aggregation)
Counters and average power demand values
● A number of energy counters record active, reactive and apparent energy.
● Calculation and storage of the average demand in the last measuring period for active
power and reactive power for simple generation of load profiles using software
(programmable measurement period of between 1 and 60 min.).
Display and operator control
● LED for Ethernet communication, active energy pulse indicator, Power ON/OFF and
overvoltage.
● powerconfig from Version 3.7
● powermanager
● Web server (HTTP)
Memory
● Device parameter settings are permanently stored in the device memory.
● Extreme values (maximum or minimum) are permanently stored in the internal device
memory. Values can be reset via powerconfig or Modbus command.