Commissioning
6.3 Parameterizing the device
"Result Logic Array" parameter
The device can be used to monitor the violation of up to 6 limit values. If a limit value is
violated, specific actions can be triggered. In addition, the limit values can be combined with
each other using a logic operation. The result of the logic operation can also be used to
trigger specific actions.
Selection
Logic operators Possibility of logic operations on limit values. Logic operations are
Example:
LIM0, LIM1, LIM3 and LIM5 are to be linked to one another with the following logic:
Selection of the operators:
op0: AND (Λ)
op1: AND (Λ)
op2: ----
op3: AND (Λ)
op4: ----
op5: OR (V)
52
Range
always performed on the limit values according to the following
formula:
(((((op0 LIM0 op1 LIM1) op2 LIM2) op3 LIM3) op4 LIM4) op5
LIM5) = RLO
LIM0: Limit 0
LIM1: Limit 1
LIMx Limit x
op: Logic operator AND / OR / ----
"----": Limit value is not combined with any other limit value.
The result of the logic operation is the "LIMIT LOGIC".
Equipment Manual, 02/2020, L1V30415168B-02