Appendix
A.1 Modbus
A.1.2

Exception codes

Overview
Table A- 2
Modbus exception codes
Exception codes
01
02
03
04
F0
112
Name
Meaning
Illegal Function
Illegal function:
Illegal Data Address
Illegal data address:
This address is not permissible for the slave.
This is the case, for example, if the combination
of start offset and transfer length is invalid.
Illegal Data Value
Illegal data value:
The request contains a data value that is not
permissible for the slave. This indicates an error
in the remaining structure of a complex request,
e.g. an incorrect data length.
Slave Device Failure
Error in processing the data:
An indefinite error occurred when the slave
attempted to execute the requested action.
Write Protection ON
The action has been rejected because the write
protection is set.
The function code in the request is not a
permissible action for the slave.
The slave is in a status in which it cannot
process a request of this type. This is the
case, for example, if it has not yet been con-
figured and is requested to return register
values.
Remedy
Check which function
codes are supported.
Check the offset and
the number of regis-
ters.
Check that the speci-
fied offset and the
specified data length in
the command are
correct.
Check that the speci-
fied offset and the
specified data length in
the command are
correct.
Deactivate the write
protection.
PAC3120 and PAC3220
Equipment Manual, 10/2019, L1V30425208F-01