PROFIenergy
7.2 Response of analog output module
Mode parameter
The following table shows the "Mode" parameter.
Table 7- 1
Element
Mode
As there is only one actuator supply U
1
a "pause" if all channel parameters have been set to switch off.
30
Mode parameter
Code
0
: PE_MODE_PROCEED
D
1
: PE_MODE_SHUTDOWN
D
3
: PE_MODE_LAST_VALUE
D
4
: PE_MODE_SUBST_VALUE
D
Explanation
Proceed at "pause"
Value status "GOOD"
Switch off at "pause"
Actuator supply U
Outputs de-energized
Value status "BAD"
Last value at "pause"
Pause substitute value: Last output value:
Value status "BAD"
Substitute value at "pause"
Pause substitute value: Configured pause
substitute value
Value status "BAD"
for all channels, the supply can only be switched off during
A
Analog output module AQ 4xU/I 4xM12 (6ES7145-5ND00-0BA0)
switched off
A
Manual, 07/2019, A5E38687953-AB