Substitute value
With this parameter, you set substitute values for the analog outputs.
The table below shows the permitted value ranges for the substitute values:
Table 4- 3
Output type
Current
Voltage
Analog output module AQ 4xU/I 4xM12 (6ES7145-5ND00-0BA0)
Manual, 07/2019, A5E38687953-AB
Permissible substitute values for the output ranges
Output range
±10 V
0 V to 10 V
1 V to 5 V
±20 mA
0 mA to 20 mA
4 mA to 20 mA
Parameters/address space
4.3 Explanation of the parameters
Valid substitute value
-32512 to 32511
0..32511
-6912 to 32511
-29031..29030
0..29030
-692 to 29376