Technical specifications
Article number
Errors/accuracies
Output ripple (relative to output range, band-
width 0 to 50 kHz), (+/-)
Linearity error (relative to output range), (+/-)
Temperature error (relative to output range),
(+/-)
Crosstalk between the outputs, max.
Repeat accuracy in steady state at 25 °C (rela-
tive to output range), (+/-)
Operational error limit in overall temperature
range
Voltage, relative to output range, (+/-)
Current, relative to output range, (+/-)
Basic error limit (operational limit at 25 °C)
Voltage, relative to output range, (+/-)
Current, relative to output range, (+/-)
Interrupts/diagnostics/status information
Substitute values connectable
Alarms
Diagnostic alarm
Diagnostic messages
Wire-break
Short-circuit
Diagnostics indication LED
Channel status display
for module diagnostics
Potential separation
between the load voltages
Potential separation channels
between the channels
between the channels and backplane bus
between the channels and the power sup-
ply of the electronics
Isolation
Isolation tested with
Degree and class of protection
IP degree of protection
26
6ES7145-5ND00-0BA0
0.02 %
0.1 %
0.005 %/K
-70 dB
0.03 %
0.25 % from 55 °C to -25 °C and 0.35 % to -30 °C
0.25 %
0.15 %
0.15 %
Yes; channel by channel, parameterizable
Yes; Parameterizable
Yes; channel-by-channel, only for output type
"current"
Yes; Actuator supply module by module; channel
by channel for output type "voltage"
Yes; Green LED
Yes; Green/red LED
Yes
No
Yes
No
707 V DC (type test)
IP65/67
Analog output module AQ 4xU/I 4xM12 (6ES7145-5ND00-0BA0)