Start-Up; General - Carrier Omnizone 50XCA06 Installation, Start-Up And Service Instructions Manual

Air-cooled indoor self contained systems
Hide thumbs Also See for Omnizone 50XCA06:
Table of Contents

Advertisement

START-UP

CAUTION
To prevent injury, ensure that ducting or wire fan guards are
installed on the condenser fan before starting the unit.

General

Complete the start-up checklist on pages CL-1 and CL-2 before
attempting system start-up.
1.
Set indoor thermostat system switch to OFF position and fan
switch to AUTO position.
2.
Check all electrical connections, fuses, starter and pressure
control resets.
3.
Check operation of evaporator fan motor and ensure fan rota-
tion is correct. If rotation needs to be reversed, disconnect
CFM
0.00
0.10
Rpm Bhp
Rpm
Bhp Rpm
2100
466
0.21
548
0.30
2200
488
0.24
567
0.34
2300
511
0.28
586
0.37
2400
533
0.31
605
0.41
2500
555
0.36
625
0.46
2600
577
0.40
644
0.51
2700
599
0.45
664
0.56
2800
621
0.50
684
0.61
2900
644
0.56
704
0.67
3000
666
0.61
725
0.74
3100
688
0.68
745
0.80
3200
710
0.75
766
0.88
3300
732
0.82
786
0.95
3400
755
0.89
807
1.03
3500
777
0.98
828
1.12
CFM
1.00
1.10
Rpm Bhp
Rpm
Bhp Rpm
2100 1084
1.54
1131
1.71 1177
2200 1090
1.59
1136
1.77 1182
2300 1097
1.65
1142
1.83
2400 1104
1.71
1149
1.90
2500 1112
1.78
1156
1.97
2600 1120
1.85
2700 1130
1.93
2800
2900
3000
3100
3200
3300
3400
3500
LEGEND
Bhp — Brake Horsepower
ESP — External Static Pressure
Table 4 — Condenser Fan Performance — 50XCA06 Units
0.20
0.30
Bhp Rpm
Bhp Rpm Bhp
623
0.40
692
0.51
639
0.44
706
0.55
656
0.48
721
0.60
673
0.53
736
0.64
690
0.57
751
0.70
708
0.62
767
0.75
725
0.68
783
0.81
744
0.74
800
0.87
762
0.80
817
0.94
781
0.87
834
1.01
799
0.94
852
1.08
818
1.01
869
1.16
838
1.09
887
1.24
857
1.18
905
1.33
876
1.27
924
1.42
1.20
1.30
Bhp Rpm
Bhp Rpm Bhp
1.90
1.96
main power and switch any 2 leads on the load side of the dis-
connect switch.
4.
Adjust fan speed. Units are belt-driven and allow for a wide
range of static and airflow requirements. It may be necessary
to adjust the condenser airflow to account for these inlet con-
ditions. Inadequate airflow will result in poor unit perfor-
mance and possible nuisance tripping of high-pressure
switches. If an airflow is not specified, use the nominal air-
flow from Tables 4-15 and adjust fan speed to compensate for
actual job conditions. Use Table 1 to determine proper fan
speed. If the unit trips on high pressure due to high condens-
ing temperature it may be necessary to increase the fan speed
and condenser airflow.
5.
The outdoor-air fans cycle with the compressor. Be sure fans
are running during compressor operation.
ESP (in. wg)
0.40
0.50
Rpm Bhp
Rpm Bhp
757
0.63
818
0.76
876
769
0.68
829
0.81
885
782
0.72
840
0.86
896
796
0.77
852
0.91
907
810
0.83
865
0.97
918
824
0.89
878
1.03
930
839
0.95
892
1.09
943
854
1.01
906
1.16
956
870
1.08
920
1.23
969
886
1.15
935
1.31
983
902
1.23
950
1.39
997
918
1.31
966
1.47 1011
935
1.40
981
1.56 1026
952
1.49
997
1.66 1041
969
1.59 1014
1.76 1057
ESP (in. wg)
1.40
1.50
Rpm Bhp
Rpm Bhp
NOTES:
1. Units are available with several motor hp options. Refer to Table 1.
2. Static pressure losses for any options or accessories must be
applied to external static pressure before entering the fan perfor-
mance table.
3. Interpolation is permitted; extrapolation is not.
4. Fan performance is based on unit casing, and wet DX (direct
expansion) coil losses at sea level.
21
0.60
0.70
0.80
Rpm
Bhp Rpm
0.90
931
1.05
984
0.95
940
1.10
992
1.00
949
1.15 1000
1.06
959
1.21 1009
1.12
969
1.27 1018
1.18
980
1.34 1029
1.25
992
1.41 1039
1.32 1004
1.48 1050
1.39 1016
1.56 1062
1.47 1029
1.64 1074
1.55 1042
1.72 1086
1.64 1056
1.81 1099
1.73 1070
1.91
1.83
1.93
1.60
1.70
1.80
Rpm
Bhp Rpm
0.90
Bhp Rpm
Bhp
1.20 1035
1.37
1.26 1042
1.42
1.31 1049
1.48
1.37 1057
1.54
1.43 1066
1.60
1.50 1075
1.67
1.57 1085
1.75
1.65 1095
1.83
1.73 1106
1.91
1.81 1117
1.99
1.90
1.99
1.90
Bhp Rpm
Bhp