SPECTRA
Trumpet Horn Flashing Filament
5W @ 1Hz BA9s Filament Bulb.
IP Rating: IP65
Temp: -25 C to +50 C
Unit weight: 219g
CE
Order code Voltage
H100TF024G/x 24V DC
Unit current consumption
Sounder
10mA
Beacon
250mA
H100TF048G/x, 50/60Hz 48V AC
Unit current consumption
Sounder
35mA
Beacon
110mA
H100TF115G/x, 50/60Hz 115V AC
Unit current consumption
Sounder
19mA
Beacon
35mA
H100TF230G/x , 50/60Hz 230V AC
Unit current consumption
Sounder
10mA
Beacon
25mA
B
ATTENTION: Installation must be carried out by an electrician in compliance
with the latest codes and regulations.
ATTENTION: Disconnect from power source before
installation or service to prevent electric shock.
ATTENTION: Lens on unit will be hot
allow to cool prior to removal.
H100 TF
Dimensions :
85 x 241.2mm
1.5mm² terminals
Cable entry: 1 x 5-7mm push
through grommet
x = Lens colour
R = Red A = Amber
B = Blue C = Clear
G = Green Y = Yellow
Bulb Type BA9s
E2S Part No.
Version
BR10245B
24V 5W
BR10485B
48V 5W
BR101305B
115V 5W
BR102305B
230V 5W
Tel : +44 (0)2 8743 8880 Fax : +44 (0)20 8740 4200
mail : sales@e2s.com
web : www.e2s.com
D
SOUNDER
PCB
N/-
N/-
L/+
TERMINAL
BLOCK
N~
-
warning signals
C
warning signals
1
Beacon
1
1
2
1
3
L/+ E
MAX
MIN
VOLUME CONTROL
SHOWN SET TO MAX
TONE
1
2
3
L~
+
2
TONE 1
BUZZER
3
2
TONE 2
1200/500Hz
SWEEPING
3
@ 1Hz
2
TONE 3
800/1000Hz
3
@ 7Hz
FREQUENCY DESCRIPTION
BUZZER
1200/500Hz  SWEEPING @ 1Hz
800/1000Hz @ 7Hz
warning signals
D152-00-301-IS_SHT1_ISSUE_C
warning signals

Advertisement

loading

Summary of Contents for E2S Spectra H100 TF

  • Page 1 @ 1Hz SOUNDER H100TF024G/x 24V DC Unit current consumption • Sounder 10mA Bulb Type BA9s • Beacon 250mA E2S Part No. Version TONE 3 800/1000Hz H100TF048G/x, 50/60Hz 48V AC @ 7Hz BR10245B 24V 5W Unit current consumption BR10485B 48V 5W L/+ E •...
  • Page 2 INPUT N~(FROM BEACON) -(FROM BEACON) L~(FROM BEACON) +(FROM BEACON) Tel : +44 (0)2 8743 8880 Fax : +44 (0)20 8740 4200 mail : sales@e2s.com web : www.e2s.com warning signals warning signals PLACE THE HEADER PIN TO REQUIRED TONE SEE SHEET 1,FOR DETAIL.

This manual is also suitable for:

Spectra h100tf024Spectra h100tf048Spectra h100tf115Spectra h100tf230