Heating System Types Heating Systems 1 And 2 - Viessmann VITOTRONIC 200-H Installation And Service Instructions Manual

Digital indoor/outdoor heating circuit control unit
Table of Contents

Advertisement

Heating system designs
System version 1
Direct connection to heating circuit loop
H
6
A Vitotronic 200-H
B Power/pump module
C Heating circuit
D Supply manifold
E Return manifold
F Power supply 120 VAC, 6FLA
! Outdoor temperature sensor (ATS)- X3 socket
(see page 7)
? Supply temperature sensor - X6 socket (see page 7)
sÖ Heating circuit pump (wired from PPM)
fÖ Power supply to Vitotronic 200-H (wired from PPM)
aVD Connection for external controls - X5 socket
(see page 13)
Electrical connection
B Power/pump module
G Power supply 120 VAC, 6FLA
H Heating pump
I High limit aquastat (optional)
Note: Remove jumper from terminals L-L when making
limit connection
Specification
Setting range: 0 to 80ºC / 32 to 176ºF
Switching differential
Immersion thermostat:
Contact thermostat:
Electro-mechanical limit aquastat, according to the liquid
expansion principle, switches the heating circuit pump
OFF, when the set value has been exceeded.
In such cases the supply temperature reduces only
slowly, e.g. it may be several hours before the system
restarts again automatically.
max. 11ºC / 22ºF
max. 14ºC / 27ºF