5500 Series Power Operator

Components

On/Off Switch

General Information

UL labeled fire or smoke barrier door assemblies require that the 120VAC (60Hz) power input to the 5500 door
operator be supplied through normally closed alarm contacts of the alarm system / alarm panel.
Power input to 5500 door operator must be 120VAC (60Hz) to terminals HOT and COM at Power Inputs terminal
strip. Earth ground (GND) to green screw on backplate.
All wiring must conform to standard wiring practice in accordance with national and local wiring codes.
Unit is Non-Handed.
Door must swing freely through the entire opening and closing cycle before beginning the installation.
Use of an auxiliary door stop (by others) is always recommended.
An incorrectly installed or improperly adjusted door operator can cause property damage or personal injury. These
instructions should be followed to avoid the possibility of misapplication or misadjustment.

Technical Data

Input power:
Power consumption:
Fuse:
Door width:
Door weight:
Door opening angle:
Hold open time:
Copyright © 2020, ASSA ABLOY Accessories and Door Controls Group, Inc. All rights reserved. Reproduction in whole or
in part without the express written permission of ASSA ABLOY Accessories and Door Controls Group, Inc. is prohibited.
80-9355-0001-020 Rev 1 08/20
120VAC Electrical Connections,
Activation Inputs, Fuse
120VAC, 60Hz
.6 amps
3 amps
28" - 48" Max. (71-122 cm)
100-250 lb Max. (43-113 kg)
up to 120°; Manually to 180°
5-30 seconds (A.D.A. 5 seconds min.)
WARNING: Make sure (120V, 60Hz) input
power is turned OFF at facility's main circuit
breaker before proceeding with installation
Motor Assembly
1600 Series
Closer Body
Open/Closed
Chain
Pinion Extension/
Clutch Assembly
Notes:
Permanent wiring is to be implemented as required by
local codes.
Activation devices: push plates, access control, mats,
touchless wall switches, etc.
Maximum wire size is:
12AWG at terminals HOT and COM (120VAC; 60Hz)
14AWG at terminals A1, A2, R1, R2
Rate of operation shall not exceed 300 cycles of opening
and closing per hour.
Inverter
Reed Switch
Positioning
Magnets
Backplate
3