Boiler Configuration Level - Immergas VICTRIX PRO 35 1 I Instruction For Technician And Installer

Thermoregulation system
Hide thumbs Also See for VICTRIX PRO 35 1 I:
Table of Contents

Advertisement

Boiler configuration level.

The parameters of this section are referred to heat generator types and to their specific characteristics.
PARAmETER
Description
01
Heat generator type
03
Min. heat generator temperature
04
Max. heat generator temperature
17
Max. flue gas temperature
25
Max. external temperature lock
26
Initial delivery temperature increase for standard loading
29
Forced heat dissipation
Regulation
Setting range / Parameters
5
OFF
no heat generators
1
1 step gas generator
2
2 steps gas generator
3
two 1 step gas generators
4
Variable burner
5
condensing
20 °C
5 °C ... Max. temperature
85 °C
Min. temperature ... 95 °C
150 °C
50 ... 500 °C
OFF
OFF, -20 ... 30 °C
0
0 ... 60 K
OFF
OFF
1
Into the d.h.w. storage tank
2
Into the heating circuits
3
Into the buffer