LOVATO ELECTRIC ATL 500 Instruction Manual

LOVATO ELECTRIC ATL 500 Instruction Manual

Automatic transfer switch controller
Hide thumbs Also See for ATL 500:

Advertisement

Quick Links

LOV TO ELECTRIC S.P. .
24020 GORLE (BERGAMO) ITALIA
VIA DON E. MAZZA, 12
TEL. 035 4282111
L
E
E-mail info@
ovato
lectric.com
L
E
Web
www.
ovato
lectric.com
W RNING!
– Carefully read the manual before the installation or use.
– This equipment is to be installed by qualified personnel, complying to current standards, to avoid
damages or safety hazards.
– Before any maintenance operation on the device, remove all the voltages from measuring and supply inputs and short-
circuit the CT input terminals.
– The manufacturer cannot be held responsible for electrical safety in case of improper use of the equipment.
– Products illustrated herein are subject to alteration and changes without prior notice. Technical data and descriptions
in the documentation are accurate, to the best of our knowledge, but no liabilities for errors, omissions or
contingencies arising there from are accepted.
– A circuit breaker must be included in the electrical installation of the building. It must be installed close by the
equipment and within easy reach of the operator. It must be marked as the disconnecting device of the equipment:
IEC /EN 61010-1 § 6.11.3.1.
– Clean the device with a soft dry cloth; do not use abrasives, liquid detergents or solvents.
TTENTION !
– Lire attentivement le manuel avant toute utilisation et installation.
– Ces appareils doivent être installés par un personnel qualifié, conformément aux normes en vigueur en
matière d'installations, afin d'éviter de causer des dommages à des personnes ou choses.
– Avant toute intervention sur l'instrument, mettre les entrées de mesure et d'alimentation hors tension et court-circuiter
les transformateurs de courant.
– Le constructeur n'assume aucune responsabilité quant à la sécurité électrique en cas d'utilisation impropre du
dispositif.
– Les produits décrits dans ce document sont susceptibles d'évoluer ou de subir des modifications à n'importe quel
moment. Les descriptions et caractéristiques techniques du catalogue ne peuvent donc avoir aucune valeur
contractuelle.
– Un interrupteur ou disjoncteur doit être inclus dans l'installation électrique du bâtiment. Celui-ci doit se trouver tout
près de l'appareil et l'opérateur doit pouvoir y accéder facilement. Il doit être marqué comme le dispositif
d'interruption de l'appareil : IEC/ EN 61010-1 § 6.11.3.1.
– Nettoyer l'appareil avec un chiffon doux, ne pas utiliser de produits abrasifs, détergents liquides ou solvants.
CHTUNG!
– Dieses Handbuch vor Gebrauch und Installation aufmerksam lesen.
– Zur Vermeidung von Personen- und Sachschäden dürfen diese Geräte nur von qualifiziertem
Fachpersonal und unter Befolgung der einschlägigen Vorschriften installiert werden.
– Vor jedem Eingriff am Instrument die Spannungszufuhr zu den Messeingängen trennen und die Stromwandler
kurzschlie en.
– Bei zweckwidrigem Gebrauch der Vorrichtung übernimmt der Hersteller keine Haftung für die elektrische Sicherheit.
– Die in dieser Broschüre beschriebenen Produkte können jederzeit weiterentwickelt und geändert werden. Die im
Katalog enthaltenen Beschreibungen und Daten sind daher unverbindlich und ohne Gewähr.
– In die elektrische Anlage des Gebäudes ist ein Ausschalter oder Trennschalter einzubauen. Dieser muss sich in
unmittelbarer Nähe des Geräts befinden und vom Bediener leicht zugänglich sein. Er muss als Trennvorrichtung für das
Gerät gekennzeichnet sein: IEC/ EN 61010-1 § 6.11.3.1.
– Das Gerät mit einem weichen Tuch reinigen, keine Scheuermittel, Flüssigreiniger oder Lösungsmittel verwenden.
DVERTENCI
– Leer atentamente el manual antes de instalar y utilizar el regulador.
– Este dispositivo debe ser instalado por personal cualificado conforme a la normativa de instalación
vigente a fin de evitar daños personales o materiales.
– Antes de realizar cualquier operación en el dispositivo, desconectar la corriente de las entradas de alimentación y
medida, y cortocircuitar los transformadores de corriente.
– El fabricante no se responsabilizará de la seguridad eléctrica en caso de que el dispositivo no se utilice de forma
adecuada.
– Los productos descritos en este documento se pueden actualizar o modificar en cualquier momento. Por consiguiente,
las descripciones y los datos técnicos aquí contenidos no tienen valor contractual.
– La instalación eléctrica del edificio debe disponer de un interruptor o disyuntor. Éste debe encontrarse cerca del
dispositivo, en un lugar al que el usuario pueda acceder con facilidad. Además, debe llevar el mismo marcado que el
interruptor del dispositivo (IEC/ EN 61010-1 § 6.11.3.1).
– Limpiar el dispositivo con un trapo suave; no utilizar productos abrasivos, detergentes líquidos ni disolventes.
UPOZORNĚNÍ
AVERTIZARE!
GB
UTOM TIC TR NSFER SWITCH CONTROLLER
Instructions manual
DE
UTOM TISCHES NETZUMSCH LTSTEUERGERÄT
Betriebsanleitung
TL 500
TTENZIONE!
– Leggere attentamente il manuale prima dell'utilizzo e l'installazione.
– Questi apparecchi devono essere installati da personale qualificato, nel rispetto delle vigenti normative
impiantistiche, allo scopo di evitare danni a persone o cose.
– Prima di qualsiasi intervento sullo strumento, togliere tensione dagli ingressi di misura e di alimentazione e
cortocircuitare i trasformatori di corrente.
– Il costruttore non si assume responsabilità in merito alla sicurezza elettrica in caso di utilizzo improprio del dispositivo.
– I prodotti descritti in questo documento sono suscettibili in qualsiasi momento di evoluzioni o di modifiche. Le
descrizioni ed i dati a catalogo non possono pertanto avere alcun valore contrattuale.
– Un interruttore o disgiuntore va compreso nell'impianto elettrico dell'edificio. Esso deve trovarsi in stretta vicinanza
dell'apparecchio ed essere facilmente raggiungibile da parte dell'operatore. Deve essere marchiato come il dispositivo
di interruzione dell'apparecchio: IEC/ EN 61010-1 § 6.11.3.1.
– Pulire l'apparecchio con panno morbido, non usare prodotti abrasivi, detergenti liquidi o solventi.
UW G !
ПРЕДУПРЕЖДЕНИЕ!
DİKKAT!
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ATL 500 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for LOVATO ELECTRIC ATL 500

  • Page 1 UTOM TIC TR NSFER SWITCH CONTROLLER Instructions manual LOV TO ELECTRIC S.P. . UTOM TISCHES NETZUMSCH LTSTEUERGERÄT 24020 GORLE (BERGAMO) ITALIA VIA DON E. MAZZA, 12 Betriebsanleitung TEL. 035 4282111 E-mail info@ ovato lectric.com www. ovato lectric.com TL 500 W RNING! TTENZIONE! –...
  • Page 2: Table Of Contents

    INTRODUCTION VORWORT ATL 500 is an automatic transfer switch controller for the automatic or manual switching of the load from ATL 500 ist ein automatischer Netzumschalter zum automatischen oder manuellen Umschalten des the MAIN LINE to a stand-by or emergency SECONDARY LINE and vice versa.
  • Page 3: Front Leds

    POWER-UP EINSCHALTEN DER SPANNUNGSVERSORGUNG – ATL 500 has self-seeking power supply from the two measurement inputs 110...240VAC. It means – ATL 500 ist mit einer doppelten Selbstversorgung (self-seeking) 110...240VAC ausgestattet. Das that it is self-powered by automatically selecting the best line available between LINE 1 and LINE 2, bedeutet, dass es sich selbstständig macht, indem es automatisch die beste Leitung zwischen den...
  • Page 4: Programmable Inputs And Outputs

    Device entsperrt (aktiv) sein. – If a password is set in the ATL 500 (see menu M02 - Password), this must be known, otherwise the – Wurde im ATL 500 ein Password eingegeben (siehe Menü M02 - Password), muss dieses bekannt access to parameters will not be possible (the App requires to entry the password).
  • Page 5 LOVATO NFC App: QR code for the download of the LOVATO NFC App: – In the following table there is the lists of available submenus: – In der nachstehenden Tabelle sind die verfügbaren Menüs aufgeführt: Code MENU DESCRIPTION Code MENÜ BESCHREIBUNG GENERAL System specifications...
  • Page 6: Parameters Table

    ATL 500 is powered OFF, so no alarm will be generated. Hinweis: wenn beide Netze vollständig fehlen, deaktiviert sich der ATL 500, so dass kein Alarm ausgelöst P04.07 – If this parameter is enabled, after a transfer to the secondary line, restore to main line does not wird.
  • Page 7 M05 - LINE 1 CONTROL / KONTROLLE NETZ 1 Default Range P05.01 MIN voltage limit / Spannungsgrenze MIN 70-100 P05.02 MIN voltage pick-up / Grenzwert MIN Rücksetzung 70-100 P05.03 MIN voltage delay / Verzögerung MIN-Spannung POT/0-600 P05.04 MAX voltage limit / Grenzwert MAX-Spannung 100-130 / OFF P05.05 MAX voltage pick-up / Grenzwert MAX Rücksetzung...
  • Page 8: Alarms

    1 Blinkvorgang = Alarm A01, 2 Blinkvorgänge = Alarm A02, 3 Blinkvorgänge = Alarm A03, usw.). – Alarms can be reset by pressing the MAN key. Note. After pressing MAN key the ATL 500 goes in Die Bedeutung des Alarms ist in der larmtabelle beschrieben.
  • Page 9: Alarms Description

    Deaktiviert Eingang deaktiviert LINE 1 feedback Auxiliary contact informing the ATL 500 of the open/closed status of LINE 1 Feedback NETZ 1 Hilfskontakt, der dem ATL 500 angibt, ob das Umschaltgerät von NETZ 1 changeover device. If this signal is not connected, ATL 500 considers the geöffnet/geschlossen ist.
  • Page 10: Programmable Outputs Function Table

    INSTALLATION INSTALLATION – ATL 500 ist für die Unterputzmontage bestimmt. Bei korrektem Einbau und mit der optionalen – ATL 500 is designed for flush-mount installation. With proper mounting, it guarantees with the Dichtung EXP80 01 wird Schutzart IP65 an der Vorderseite garantiert.
  • Page 11: Wiring Diagrams

    WIRING DIAGRAMS ANSCHLUSSPLÄNE Control of contactors – three-phase connection Dreiphasenanschluss – Schützsteuerung Note: for two-phase connection, connect the terminals L1-L2-N. Anmerkung: für den zweiphasigen Anschluss die Klemmen L1-L2-N benutzen. Parameter setting for the wiring diagram in picture Programmierung der Parameter für den abgebildeten Schaltplan Terminal Parameter code Setting...
  • Page 12 Dual power supply implementation with auxiliary voltage control for motorized changeover by Ausführung Dual Power Supply mit Kontrolle der Hilfsspannung, motorisierter Umschalter mittels LOVATO Electric dual power supply relay code ATL DPS1 Vorrichtung LOVATO Electric Code ATL DPS1 ATL DPS1...
  • Page 13: Terminals Position

    TERMINALS POSITION KLEMMENANORDNUNG L1 L2 L3 N L1 L2 L3 N LINE 1 LINE 2 110-240V~ LN 110-240V~ LN 190-415V~ 3N 190-415V~ 3N 50/60Hz 50/60Hz OUT1 - OUT3 B300 / 250V~ 8A AC1 / 1A 30V= PILOT DUTY MECHANICAL DIMENSIONS AND FRONT PANEL CUT-OUT [mm] MECHANISCHE ABMESSUNGEN UND BOHRUNG DER PLATTE [mm] 43.3...
  • Page 14: Technical Characteristics

    TECHNICAL CHARACTERISTICS TECHNISCHE MERKMALE LINE 1 and LINE 2 voltage inputs: terminals 1-4 and 5-8 Spannungseingänge NETZ 1 und NETZ 2 Klemmen 1-4 und 5-8 Rated voltage 110...240V~ LN / 190...415V~ 3N Nennspannung 110...240V~ LN / 190...415V~ 3N Operating voltage range 90...300V~ LN / 155...519V~ 3N Spannungsbetriebsgrenzen 90...300V~ LN / 155...519V~ 3N...