SECTION 7.1: Operation Mode (Switches 1 and 2)
DN 1561
Note:  Labeled as Operation Mode but is actually a Monitoring Operation Mode.
Monitoring is an added layer of communication between the control and the sensor. The control will send a signal to the sensor. The
sensor performs a self-diagnostic test, then sends a signal back to the control confirming proper operation.
The Monitoring Operation Mode (set by dip switches 1 and 2) determines which rows of presence detection are active and which
are applied to the monitoring function. Active rows are not the same as rows that are monitored. Rows can be active (able to tell the
Table 5 Standard Monitoring Operation Modes
control to open the door) but not be applied to the Monitoring function.
Operation Mode
1
2
Normal
Doorway 2
Doorway 1
1st Row OFF
SECTION 7.2: Output Logic (Switch 3)
Note:  Ensure both the Acusensor M and the Control is set for N.O. or N.C.
When a presence is detected within a monitored area, the control automatically sends a pulse to Input Logic. Output Logic
Table 6 Output Status
automatically responds by opening the door.
Output Logic
3
Definition
N.O.
Normally
Open
N.C.
Normally
Closed
12 of 28
Row 1
Row 6
Door Type Presence Detection Area
Slide
Depth Row 1 and 2
X Swing
Depth Row 1 thru 6
X Fold
Slide
Depth Row 2 and 3
Slide
Depth Row 2 and 3
Stand-by
Detecting
Presence Detec on Area
Doorway monitoring is not applied for Depth Row 3 thru 6
X Doorway monitoring works for all Depth Rows
X Fold, and Swing doors only
X Doorway monitoring works for Depth Row 1
X Doorway monitoring does not work for Depth Row 2
thru 6
X Depth Row 1 becomes inactive
X Doorway monitoring is not applied for Depth Row 2
thru 6
Action
Test Reply
(Good)
Circuit closes
Door opens
Circuit opens
Door opens
www.NabcoEntrances.com
Note:
Row 1 is the Threshold Area
Figure 6 Presence Detection Area
Monitor Description
Test Reply
Power OFF
(Error)
Rev 8-25-17