Daiichi Electronics SMLC-110L Instruction Manual page 33

Maximum (minimum) super multi-meter
Table of Contents

Advertisement

(1) 211 to 213 Measurement range setting
The measurement range of each measurement factor is set.
211
Voltage range
◆ 211 Voltage range
A voltage range (VT ratio) is setting.
Selection by + and - , set value is updated by SET .
Default setting:6600V
Voltage measurement range (34 range)
150.0V(110V)
150V (110V)
300.0V(220V/110V)
300V (220V/110V)
518V (380V/110V) (
600V (440V/110V)
627V (460V/110V) (
655V (480V/110V) (
1200V (880V/110V)
1500V (1100V/110V)
2250V (1650V/110V) (
3000V (2200V/110V)
3.00kV (2200V/110V)
4500V (3300V/110V)
4.50kV (3300V/110V)
9000V (6600V/110V)
9.00kV (6600V/110V)
◆ 212 Zero-phase voltage scale
Display ON/OFF of ×1/√ 3 is set as a scale of zero-phase voltage.
Selection by + and - , set value is updated by SET .
Default setting:×1/√ 3 display OFF
×1/√ 3
display OFF
◆ 213 Frequency range
Frequency measurement range can be selected from 45.0 to 55.0Hz /
55.0 to 65.0Hz / 45.0 to 65.0Hz. Change of this setting also sets the
analog output range of a frequency automatically simultaneously.
Selection by + and - , set value is updated by SET .
Default setting:45.0 to 65.0Hz
50:
45.0 to 55.0Hz
212
RESET/
Zero-phase
SHIFT
voltage scale
RESET/SHIFT
15.00kV (11kV/110V)
18.00kV (13.2kV/110V)
18.82kV (13.8kV/110V) (
22.50kV (16.5kV/110V) (
16
)
25.09kV (18.4kV/110V) (
30.0kV (22kV/110V)
17
)
45.0kV (33kV/110V)
17
)
90.0kV (66kV/110V)
105.0kV (77kV/110V)
150.0kV (110kV/110V)
18
)
180.0kV (132kV/110V)
210.0kV (154kV/110V)
255.0kV (187kV/110V) (
300.0kV (220kV/110V)
375.0kV (275kV/110V) (
518.2kV (380kV/110V) (
750.0kV (550kV/110V)
×1/√ 3
display ON
60:
55.0 to 65.0Hz
RESET/
213
SHIFT
Frequency range
Setting factor
19
)
20
)
21
)
16
Note(
) The full scale of bar graph is 500V.
22
(
)
17
Note(
) The full scale of bar graph is 600V.
18
Note(
) The full scale of bar graph is 2400V.
19
Note(
) The full scale of bar graph is 18.00kV.
20
Note(
) The full scale of bar graph is 24.00kV.
23
)
21
Note(
) The full scale of bar graph is 25.00kV.
24
)
22
Note(
) The full scale of bar graph is 120.0kV.
25
)
23
Note(
) The full scale of bar graph is 270.0kV.
24
Note(
) The full scale of bar graph is 400.0kV.
25
Note(
) The full scale of bar graph is 500.0kV.
New setting
Setting No.
Setting factor
Current setting
55:
45.0 to 65.0Hz
32
New setting
Current setting
Setting No.
Voltage range
Zero-phase voltage scale
Setting factor
New setting
Current setting
Setting No.
Frequency range
SMLC-213-154