(3) 131H to 133 3-phase voltage detection setting
3-phase voltage factor performs a setting of upper limit alarm value and lower limit alarm value.
131H
RESET/
3-phase voltage
SHIFT
upper limit
◆ 131H 3-phase voltage upper limit,132L 3-phase voltage lower limit
The upper limit alarm value and lower limit alarm value of 3-phase
voltage (line voltage) are setting.
Setting range. 30 to 150%(1% step) and OFF(Non use).
Selection by + and - , set value is updated by SET .
Default setting:OFF〔Non use〕(Upper limit, Lower limit)
◆ 133 Line voltage Time interval
The Time interval of a line voltage is setting.
Selection by + and - , set value is updated by SET .
Default setting:0 second
0sec
<秒>
132L
RESET/
3-phase voltage
SHIFT
lower limit
RESET/SHIFT
5sec
10sec
<秒>
<秒>
4min
3min
<分>
<分>
5min
6min
<分>
<分>
30min
25min
<分>
<分>
133
Setting No.
Line-voltage
time interval
20sec
30sec
<秒>
<秒>
2min
1min
<分>
<分>
7min
8min
<分>
<分>
20min
15min
<分>
<分>
29
New setting
Current setting
3-phase voltage upper limit
40sec
<秒>
50sec
<秒>
9min
<分>
10min
<分>
SMLC-213-154