 Disposal
Please dispose this product as industrial waste (non-combustible).
Mercury parts and a nickel-cadmium battery are not used for this product.
 Warranty period.
The warranty period of the product is one year after the date of delivery.
 Operation
Be careful with the following cautions during use.
 Use the input within the rated range. Be careful since negligence of this caution may cause troubles of the unit.
 There is a function to hold the maximum value and the minimum value with a measurement factor in this product.
The blackout this value will not be cleared by a power supply reset. However, the minimum value may be updated in
case input is not applied to a power up. Therefore the maximum value and the minimum value need to be reset of DI
after a startup, or switch operation.
For this reason, in order to recover previous minimum value, please apply input within 1 second after switching on
a power supply.
 The maximum value, a minimum value measurement factor
Measurement factor
3-phase voltage,Zero-phase voltage,Frequency
 Be careful not to touch any terminal when power is applied to the unit.
 Don't disassemble or modify this unit without any previous permission of our company, otherwise
 Setting
This unit requires setting and confirmation of the measuring range, etc. before use.
Wrong setting, if any, causes malfunction of the unit. If setting should be wrong, neither measurement nor output
becomes correct. Carefully read the instruction manual before setting the unit.
 Default settings
The case of shipment of this product, it is the following default setting. Please set according to a use condition.
1
Display combination
Alarm output setting
2
(
)
3-phase voltage
3
detection setting
Zero-phase voltage
4
detection setting
5
Backlight
6
Measurement range
the warranty does not apply to the unit any more. Also, modifications may cause troubles, a
fire, or other accidents. For specifications change, etc., please contact us.
Setting item
Pattern
Main monitor
Sub-monitor (Left)
Sub-monitor (Center)
Sub-monitor (Right)
Bar graph
Alarm 1 factor
Alarm 1 reset form
Alarm 1 test <テスト>
Alarm 2 factor
Alarm 2 reset form
Alarm 2 test <テスト>
Voltage upper limit
Voltage lower limit
Line voltage Time interval
Zero-phase voltage upper limit
Response time
Ground fault phase detection
display automatic change
Action
Brightness
Voltage range
Zero-phase voltage scale
Frequency range
Maximum value measurement
Phase voltage input
Vo 190V
Vo 110V
Pattern 1
Maximum zero-phase voltage
V(RS)
V(ST)
V(TR)
Maximum zero-phase voltage
+ Zero-phase voltage
Zero-phase voltage
AUTO <自動復帰>
OFF
AUTO <自動復帰>
OFF
OFF
0 second <秒>
5280V ( /152V) 5280V ( /88V)
0.1 second <秒>
OFF
AUTO
3(Middle)
9000V (6600V/110V)
×1/√
non display
3
45.0 to 65.0Hz
2
SMLC-213-154
Minimum value measurement
Line voltage input
Vo 190V
Vo 110V
Pattern 1
Maximum zero-phase voltage
V(RS)
V(ST)
V(TR)
Maximum zero-phase voltage
+ Zero-phase voltage
Zero-phase voltage
AUTO <自動復帰>
OFF
AUTO <自動復帰>
OFF
OFF
0 second <秒>
5280V ( /152V) 5280V ( /88V)
0.1 second <秒>
OFF
AUTO
3(Middle)
9000V (6600V/110V)
×1/√
non display
3
45.0 to 65.0Hz