Installation Example
When no obstruction exists in the
blow-out side
150 mm or wider
Stacked installation
150 mm or wider
In the case of face-to-face installation
600 mm or wider
300 mm or wider
When an obstruction exists in the
blow-out side
(500 + h) mm or wider
When installing next to a top-blow
refrigeration unit
( 500 + h ) mm or wider
Avoid direct entry of the blow-out heat into the heat
exchanger of the top-blow refrigeration unit. When
installation cannot be avoided, install a partition plate.
3500 mm or wider
EN - 16
Unit depth
Dimension or below
h
Partition plate
h