1. Safety Precautions Read the following “SAFETY PRECAUTIONS” carefully before perform any servicing. Electrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating and main circuit for the model installed. ...
Page 4
19. Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electrical shock or fire. 20. Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury.
2. Specifications WH-SHF09F3E5 WH-UH09FE5 Item Unit Outdoor Unit Performance Test Condition EN14511 Condition A7W35 A2W35 (Ambient/Water) 9.00 9.00 Heating Capacity BTU/h 30700 30700 kcal/h 7740 7740 4.64 3.45 kcal/hW 3.99 2.97 dB (A) Noise Level Power Level dB Air Flow...
Page 6
Item Unit Running Current 12.5 Maximum Current For Heat Pump System 28.5 Power Factor Power factor means total figure of compressor and outdoor fan motor. Number of core Power Cord Length m (ft) Thermostat Electronic Control Protection Device Electronic Control Item Unit Indoor Unit...
WH-SHF12F6E5 WH-UH12FE5 Item Unit Outdoor Unit Performance Test Condition EN14511 Condition A7W35 A2W35 (Ambient/Water) 12.00 12.00 Heating Capacity BTU/h 41000 41000 kcal/h 10320 10320 4.46 3.26 kcal/hW 3.84 2.80 dB (A) Noise Level Power Level dB Air Flow /min (ft /min) 80.0 (2830) Refrigeration Control Device...
Page 8
Item Unit Running Current 12.9 17.2 Maximum Current For Heat Pump System 29.0 Power Factor Power factor means total figure of compressor and outdoor fan motor. Number of core Power Cord Length m (ft) Thermostat Electronic Control Protection Device Electronic Control Item Unit Indoor Unit...
3. Features Inverter Technology - Energy saving High Efficiency Compact Design Environment Protection - Non-ozone depletion substances refrigerant (R407C) Long Installation Piping - Long piping up to 30 meter with height difference 20 meter - Flexible 4-way piping for outdoor unit ...
4. Location of Controls and Components Indoor Unit 4.1.1 Location of Control Water pressure gauge • Do not press or hit the glass cover using hard and sharp objects. Failure to do so may cause damage to the unit. • Ensure that the water pressure is between 0.05 and 0.3 MPa (0.1 MPa = 1 bar).
Page 11
4.1.2 To adjust initial settings Dealer Select menus and determine settings according to the system available in the household. It is recommended that all alterations of settings are done by an authorised dealer or specialist. Operation LED Display • After initial installation, you may manually adjust the settings. The initial setting remains active until the user changes it.
Page 12
Operation/settings to be done only by the authorised dealer/specialist. Dealer Operation/settings to be done by the authorised dealer/specialist or user. User Booster Heater To activate or deactivate the water tank’s booster heater. Note: If NO is selected, menu 10 is skipped. Booster Heater Delay Timer 20 minutes ~ To delay time for the booster heater to activate while the system is heating up...
Page 13
4.1.3 How to use User The system is turned off by an external switch. Turn on or off the system Press When the system is ON, the operation LED is lit and the actual water outlet temperature and outdoor ambient temperature are shown on the display.
Page 14
Operation/settings to be done only by the authorised dealer/specialist. Dealer Operation/settings to be done by the authorised dealer/specialist or user. User Dealer Display Temperature setting System temperature setting The system controls the temperature for each menu based on the outdoor ambient temperature. •...
Page 15
User Desired temperature setting Shifting the water temperature This easily shifts the water outlet temperature if the setting is undesirable. to enter the water temperature shifting mode. to change setting. to set the desired temperature. (temperature range: -5 °C ~ 5 °C) Temperature setting <Water outlet temperature>...
Operation/settings to be done only by the authorised dealer/specialist. Dealer Operation/settings to be done by the authorised dealer/specialist or user. User User Weekly timer setting Promotes energy saving by allowing you to set up to 6 programmes in any given day. Lights up if Timer operation is selected Indicates the next timer operation programme...
Page 17
Dry Concrete Function • During construction to dry the concrete under a preset temperature. simultaneously and hold for 5 seconds until the display shows “ ”. (The display shows “ ”). to select day. Press to set the desired temperature. to confirm the selection.
Page 18
Connector name 1 phase RCCB/ELCB Water Outlet Cabinet front plate Gas Refrigerant Cabinet Liquid Refrigerant Handle (2 pieces) Water drainage Overload protector Water inlet (2 pieces for WH-SHF09F3E5 (3 pieces for WH-SHF12F6E5) Heater assembly Expansion vessel WH-SHF09F3E5 Bushing Air purge valve...
5. Dimensions Indoor Unit <Top View> <Front View> <Side View> 35 98 107 115 155 <Bottom View> 205.5 98.5 Relative position between the indoor unit and the installation plate <Front View> 213.5 213.5 140.7 140.7 Installation 306.4 Plate Indoor unit external dimensions line Unit: mm...
Max. Piping Piping Model Length Elevation Refrigerant Liquid Length Length (g/m) WH-SHF09F3E5 WH-UH09FE5 Ø15.88 mm Ø9.52 mm 5~7.5 (5/8") (3/8") WH-SHF12F6E5 WH-UH12FE5 * If piping length is over common length, additional refrigerant should be added as shown in the table.
Page 23
Room Thermo (Optional) Fan Coil Unit (Heating) Connect to Indoor Unit Panel Heater Unit (Heating) 3-Way Valve 2-Way Valve To Water Inlet Indoor Unit From WaterOutlet Indoor Unit Floor Heating Panel (Heating) Heater 1 (3kW) Cold Water Supply Solar Unit (Optional) Sanitary Tank...
Elevation Refrigerant Model near the unit. Length Length Liquid (g/m) A place where air circulation in the room is good. WH-SHF09F3E5 A place where drainage can be easily done. WH-UH09FE5 ø15.88mm ø9.52mm 5~7.5 (5/8") (3/8") A place where noise prevention is taken into...
11.3 Indoor Unit 11.3.1 How to Fix Installation Plate 11.3.3 Indoor Unit Installation The mounting wall is strong and solid enough to prevent it from vibration. 11.3.3.1 Install the Indoor Unit When connecting solar pump station cable (Unit in mm) Bolt - Wall Wall...
Page 37
Valve Kit Water Inlet Water (Field Outlet External Filter supply) (Field supply) Piping size (Torque) Model Liquid Solar Pump WH-SHF09F3E5 Station ø15.88 mm ø9.52 mm Tank Unit WH-UH09FE5 (Field supply) (5/8") (3/8") WH-SHF12F6E5 [65 N•m] [42 N•m] WH-UH12FE5 Diagram 4.1: Typical Water Piping Installation CAUTION ...
11.3.4 Connect the Cable to the Indoor Unit Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed 4 × min 4.0 or 6.0 mm flexible cord, type designation 60245 IEC 57 or heavier cord. Ensure the colour of wires of outdoor unit and the terminal no. are the same to the indoor unit’s respectively.
Page 39
Terminals on the indoor 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Lead wire cord Tank Tank External Three-way Booster Heater Room Thermostat Solar Three-way Solar Pump Sensor Controller Valve Cable Valve Cable Station Cable Cord Cable...
Page 40
The equipment’s power supply 1 complies with IEC/EN 61000-3-12 provided that the short-circuit power S greater than or equal to 1100 kW (for WH-SHF09F3E5/UH09FE5 and SHF12F6E5/UH12FE5) at the interface point between the user’s supply and the public system. It is the responsibility of the installer or user of the...
(Anchor pitch) (Unit in mm) 11.4.2 CONNECTING THE PIPING CAUTION Piping size (Torque) Model Do not over tighten, over tightening cause gas leakage. Liquid WH-SHF09F3E5 ø15.88 mm ø9.52 mm WH-UH09FE5 (5/8") (3/8") WH-SHF12F6E5 [65 N•m] [42 N•m]...
Page 42
CUTTING AND FLARING THE PIPING Please cut using pipe cutter and then remove the burrs. Remove the burrs by using reamer. If burrs is not removed, gas leakage may be caused. Turn the piping end down to avoid the metal powder entering the pipe. Please make flare after inserting the flare nut onto the copper pipes.
11.4.4 Connect the Cable to the Outdoor Unit (FOR DETAIL REFER TO WIRING DIAGRAM AT UNIT) Remove the control board cover from the unit by loosening the screw. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed (4 × 4.0 or 6.0 mm ) flexible cord, type designation 60245 IEC 57 or heavier cord.
Page 44
11.4.6 DISPOSAL OF OUTDOOR UNIT DRAIN WATER When a Drain elbow is used, please ensure to follow below: the unit should be placed on a stand which is taller than 50 mm. cover the 8 holes (ø20 mm) with Rubber cap (refer to illustration below).
12. Operation and Control 12.1 Basic Function Inverter control, which equipped with a microcomputer in determining the most suitable operating mode as time passes, automatically adjusts output power for maximum comfort always. In order to achieve the suitable operating mode, the microcomputer maintains the set temperature by measuring the temperature of the environment and performing temperature shifting.
Page 46
Heat Mode Operation Time Chart 3 ways valve 2 ways valve Open Close Heat Pump Backup Heater ID W ater Pump Solar Request Solar 3 way valve W ater Outlet Temp Tank Temp. Timer for backup Backup Heater Backup Heater heater to on back Startup Timer Startup Timer...
Page 47
12.1.3 Tank Mode Operation Control contents: 3 ways valve direction 3 ways valve switch to tank side during Tank Thermo ON condition. Switch 3 ways valve to room side when tank achieve Tank Thermo OFF temperature and SOLAR turn ON condition. ...
Page 50
12.1.4 Heat + Tank Mode Operation Setting 1: When Heating priority is set by control panel: 1. 3 ways valve control: o 3 ways valve switch to room side during External Room Thermo ON OR Solar 3 ways valve ON OR Tank Thermo OFF time, and switch to tank side at External Room Thermo OFF AND Solar 3 ways valve OFF.
Page 51
Characteristic of heat pump thermo ON/OFF under tank side condition Water Outlet Thermo condition Heat pump THERMO OFF TEMP: 1. Heat pump THERMO OFF TEMP = 63°C + [+4°C]. 2. Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 90 seconds, heat pump OFF and water pump continue ON.
Page 52
Heat + Tank Mode (Heating priority set) Under Solar Priority Set Condition: Under Solar Priority Not Set Condition:...
Page 53
Setting 2: When heating priority is not set by control panel: When Solar Priority is set/not set by control panel: 1. 3 ways valve control: 3 ways valve switch to room side during heating heat-up interval, and switch to tank side during tank heat-up interval.
Page 54
Characteristic of heat pump thermo ON/OFF under tank side condition Water Outlet Thermo condition Heat pump THERMO OFF TEMP: 1. Heat pump THERMO OFF TEMP = 63°C + [+4°C] 2. Water outlet temperature > Heat pump THERMO OFF TEMP for continuous 90 seconds, heat pump OFF but water pump continue ON.
Page 58
12.1.5 Setting Water Outlet Temperature for Heat Mode The set temperature defines the parameters for the outdoor ambient temperature dependent operation of the unit. Where by the internal water setting temperature is determined automatically depending on the outdoor temperature. The colder outdoor temperatures will result in warmer water and vice versa. The user has the possibility to shift up or down the target water temperature by control panel setting.
Page 59
12.1.6 Water Temperature Thermo Shift Setting Switchs are ignored during “PUMPDW” = ON. Switchs are ignored during “STATUS” = ON. ▲ ▼ “ ”, “ ”, ”SELECT” switch are ignored if “SETTING” = OFF. “CANCEL” switch is ignored if “SETTING” = OFF & “STATUS” = OFF. ...
12.2 Water Pump 12.2.1 Water Pump Control Once the indoor unit is ON, the water pump will be ON immediately and no error judgement for 9 minutes. However, during this 9 minutes operation, if there is any abnormality cause at outdoor or malfunction, the compressor should be OFF immediately and restart delay after 3 minutes.
Page 61
12.2.2 A-class Pump Specification Power for drive DC280-373V Pump Power for control DC15±10% Control Signal DC0V-DC6V Feedback Speed (puls signal) 4puls/rotation Control signal is analog voltage (DC0V-6V) generated by microcomputer PWM port. Microcomputer can change analog voltage by changing PWM duty. 12.2.3 Water Flow Rate Setting ...
12.2.4 Water Pump Speed Feedback Error Basically pump speed feedback is control by micon. When pump speed is below low limit or over high limit for a few seconds, micon detect pump error and system is stopped. Error detection conditions: ...
12.5 Indoor Unit Safety 12.5.1 Indoor Unit Safety Control When water pump is ON, the system will start checking flow switch status (ON/OFF). If the flow switch ON for 10 seconds, the system will check on the water inlet temperature for 10 seconds. If the water inlet temperature not exceeds 80°C, the water pump shall be continuously running with normal mode.
12.8 Indoor Back-Up Heater Control 12.8.1 Indoor Electric Heater Control Normal Heating Mode Heater On condition: a. Heater switch is ON b. After Heatpump thermo ON for [30] mins c. After water pump operate [9] mins d. Outdoor air temperature < Outdoor set temperature for heater e.
12.9 Tank Booster Heater Control 12.9.1 Tank Booster Heater Control Heating operation condition: Heater OFF Tank set temperature + Tank set temperature + [-5°C] [+2°C] Heater ON Booster heater Turn On condition: After BOOSTER HEATER DELAY TIMER fulfill during heatpump startup time in tank mode, or during switching from heating heat-up interval to tank heat-up interval in heat + tank mode (heating priority not set).
12.11 Sterilization Mode Purpose: To sterilize water tank by setting the required boiling temperature. Control start condition: Tank connection menu is set to YES by control panel. Sterilization menu is set to YES by control panel. Sterilization signal received from control panel by timer. ...
12.13 Anti Freeze Control Anti freeze protection control menu can be set YES or NO by control panel. In heatpump system, there are 3 types of anti freeze control: 1. Expansion tank anti-freeze control Expansion tank anti freeze heater ON condition: Outdoor ambient temp.
12.14 Solar Operation (Optional) 12.14.1 Solar Operation: External solar heat source signal can be connect to unit for proper control of heat source switching during tank boiling time. Control according to preset whether solar priority is set or not. When tank connection is NOT set at SETTING mode, solar operation is disabled. When Pump A (from solar pump station) is detected On through connection Y3 and Y4, then the Solar pump 3 Way Valve is requested ON (Refer to figure below).
Page 69
Solar Operation Chart in different mode and condition Tank Mode (Solar Priority SET condition) Tank Mode (Solar Priority NOT SET condition)
Page 70
Heat + Tank Mode (Heating Priority NOT SET) (Solar Priority SET condition) When solar 3 way valve turn on during Tank interval, cancel Tank interval immediately and switch 3-way valve to the After heating/cooling interval, stand by to go in tank side after solar 3 way room side and start a heating/cooling interval.
12.15 External Room Thermostat Control (Optional) Purpose: Better room temperature control to fulfill different temperature request by external room thermostat. Recommended external room thermostat: Maker Characteristic Siemen (REV200) Touch panel Siemen (RAA20) Analog Connection of external room thermostat: Wire Connection and thermo characteristic of Siemen REV200: Setting L/L1 (H) Heat Thermo...
12.16 Three Ways Valve Control Purpose: - 3 ways valve is used to change flow direction of hot water from heat pump between heating side and tank side. Control contents: 3 ways valve switch Off: During 3 ways valve switch Off time, the hot water will provide heat capacity to heating side. 3 ways valve switch On: During 3 ways valve switch On time, the hot water will provide heat capacity to tank side.
12.18 Holiday Mode Purpose: Promotes energy saving by allowing the user to stop the system during holiday and enables the system to resume at the preset temperature after holiday. Control details: Range of days can be set in holiday mode is from 1 to 999 days. After days of holiday have been set, heat pump will stop and only resume operation at 12.00am at the end of holiday countdown.
13. Protection Control 13.1 Protection Control for All Operations 13.1.1 Time Delay Safety Control The compressor will not start for three minutes after stop of operation. 13.1.2 30 Seconds Forced Operation Once the compressor starts operation, it will not stop its operation for 30 seconds. However, it can be stopped using control panel at indoor unit.
Page 75
13.1.6 Low Frequency Protection Control 2 When all the below conditions comply, the minimum compressor frequency will change to lower frequency. Temperature, T, for: Heating Outlet water (°C) T < 14 or T ≥ 48 Outdoor air (°C) T < 4 or T ≥ 24 Indoor heat exchanger (°C) T ≥...
13.2 Protection Control for Heating Operation 13.2.1 Outdoor Air Temperature Control The maximum current value is regulated when the outdoor air temperature rises above 14°C in order to avoid compressor overloading. 13.2.2 Deice Operation When outdoor pipe temperature and outdoor air temperature is low, deice operation start where outdoor fan motor stop.
14. Servicing Guide 14.1 How to Take Out Front Plate Please follow the steps below for take out front plate. Before removing the front plate of indoor unit, always switch off all power supply (i.e. indoor unit power supply, heater power supply and tank unit power supply). Remove the 2 mounting screws which located at bottom of the front plate and 1 mounting screw at the front of the plate.
14.5 How to Adjust Water Flow Rate [SERVICE MODE: 02] Before adjust the water fl ow rate, make sure that the total water volume in the installation is 50 litres minimum for heating side. The default setting is SPEED 5. Please ensure the minimum fl ow rate is not less than 13 l/min and not more than 50 l/min.
14.8 EEPROM Factory Default Data Setup Procedure This process should be done at Gemstar (and/or) PAPAMY as the last process after any inspection. This condition should be activated by pressing combination of few SW's for certain time as shown. These 3 SW's should press continuously for 5secs. (Operation should be OFF during this period) When this condition is activated, default data should be written in EEPROM.
15. Maintenance Guide In order to ensure optimal performance of the unit, checks and inspections on the unit and the field wiring must be carried out regularly. Before carried out any maintenance or repair work, and removing the front plate of heat exchanger unit, always switch off all power supply (i.e.
Page 81
Reset overload protector Overload protector serves the safety purpose to prevent the water over heating. When the overload protector trip at high water temperature, take below steps to reset it. a. Take out OLP cover. b. Use a test pen to push the centre button gently in order to reset the Overload protector. c.
16. Troubleshooting Guide 16.1 Refrigeration Cycle System In order to diagnose malfunctions, make sure that there are no electrical problems before inspecting the refrigeration cycle. Such problems include insufficient insulation, problem with the power source, malfunction of a compressor and a fan. The normal pressure of the refrigeration cycle depends on various conditions, the standard values for them are shown in the table on the right.
16.2 Relationship between the Condition of the Air-to-Water Heatpump Indoor and Outdoor Units and Pressure and Electric Current Heating Mode Condition of the Air-to-Water Heatpump indoor and outdoor Low Pressure High Pressure Electric current during operation units Water leakage or insufficient water flow rate in the system Excessive amount of refrigerant Inefficient compression...
16.3 Breakdown Self Diagnosis Function 16.3.1 Self Diagnosis Function (Three Digits Alphanumeric Code) When abnormality occur during operation, the system will stop operation, and OFF/ON control panel LED will blink and error code will display on the control panel timer display LCD. ...
16.4 Error Codes Table Diagnosis display Abnormality/Protection control Abnormality judgement Primary location to verify No abnormality detected — — Indoor/outdoor connection wire Indoor/outdoor PCB Indoor/Outdoor capacity unmatched continue for 90 sec. Specification and combination table in catalogue ...
Page 86
Diagnosis display Abnormality/Protection control Abnormality judgement Primary location to verify Outdoor air temperature sensor Outdoor air temperature sensor Continue for 5 sec. abnormality (defective or disconnected) Water inlet temperature sensor Indoor water inlet temperature sensor Continue for 5 sec. abnormality (defective or disconnected) Outdoor discharge pipe temperature...
16.5 Self-diagnosis Method 16.5.1 Connection Capability Rank Abnormality (H12) Malfunction Decision Conditions: During startup operation of heating, the capability rank of indoor checked by the outdoor is used to determine connection capability rank abnormality. Malfunction Caused: Wrong model interconnected. Wrong indoor unit or outdoor unit PCB (main) used. Faulty indoor unit or outdoor unit PCB (main).
Page 88
16.5.2 Compressor Tank Temperature Sensor Abnormality (H15) Malfunction Decision Conditions: During startup and operation of heating, the temperatures detected by the compressor tank temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue for 5 seconds.
Page 89
16.5.3 Water Pump Abnormality (H20) Malfunction Decision Conditions: During startup and operation of cooling and heating, the rotation speed detected by the IPM of water pump motor during water pump operation is used to determine abnormal water pump (feedback of rotation > 6,000rpm or < 1,000rpm).
Page 90
16.5.4 Indoor Refrigerant Liquid Temperature Sensor Abnormality (H23) Malfunction Decision Conditions: During startup and operation of heating, the temperatures detected by the indoor refrigerant liquid temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty indoor unit PCB (main).
Page 91
16.5.5 Service Valve Error (H27) Malfunction Decision Conditions: During cooling operation, when:- [a] Indoor refrigerant pipe temperature at compressor startup - present indoor refrigerant pipe temperature < 2°C [b] Present high pressure - high pressure at compressor startup < 5kg/cm **Judgment only for first time cooling operation and not during pump down operation.
16.5.6 Compressor Low Pressure Protection (H42) Malfunction Decision Conditions: During operation of heating and after 5 minutes compressor ON, when outdoor pipe temperature below -29°C or above 26°C is detected by the outdoor pipe temperature sensor. Malfunction Caused: Dust accumulation on the outdoor unit heat exchanger. Air short circuit at outdoor unit.
Page 93
16.5.7 Water Flow Switch Abnormality (H62) Malfunction Decision Conditions: During operation of heating, the water flow detected by the indoor water flow switch is used to determine water flow error. Malfunction Caused: Air trapped in water system. Faulty water pump. Water leak in system.
Page 94
16.5.8 Outdoor High Pressure Abnormality (H64) Malfunction Decision Conditions: During operation of heating, when the outdoor high pressure sensor output signal is 0Vdc or 5Vdc. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 4 times in 20 minutes.
Page 95
16.5.9 Deice Circulation Error (H65) Malfunction Decision Conditions: During startup and operation of deice (mode 2), the water flow (> 10l/min) detected by the water flow switch is used to determine deice circulation error. Malfunction Caused: Water flow in air-to-water heatpump indoor unit circuitry. Faulty indoor unit water flow switch.
Page 96
16.5.10 Indoor Backup Heater OLP Abnormality (H70) Malfunction Decision Conditions: During operation of indoor backup heater, when no power supplies to indoor backup heater or OLP open circuit. Malfunction Caused: Faulty power supply connector connection. Faulty connector connection. Faulty indoor backup heater overload protector (OLP). Faulty indoor unit PCB (main).
Page 97
16.5.11 Tank Temperature Sensor Abnormality (H72) Malfunction Decision Conditions: When tank connection is set to ON, the temperatures detected by the tank temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty indoor unit PCB (main). Abnormality Judgment: Continue for 5 seconds.
Page 98
16.5.12 Indoor-Control Panel Communication Abnormality (H76) Malfunction Decision Conditions: During standby and operation of heating, indoor-remote control error occur. Malfunction Caused: Faulty connector connection. Faulty remote control. Faulty indoor unit PCB (main).
Page 99
16.5.13 Indoor/Outdoor Abnormal Communication (H90) Malfunction Decision Conditions: During operation of heating, the data received from outdoor unit in indoor unit signal transmission is checked whether it is normal. Malfunction Caused: Faulty outdoor unit PCB (main). Faulty indoor unit PCB (main). Indoor-outdoor signal transmission error due to wrong wiring.
Page 100
16.5.14 Tank Booster Heater OLP Abnormality (H91) Malfunction Decision Conditions: During operation of tank booster heater, and tank booster heater OLP open circuit. Malfunction Caused: Faulty connector connection. Faulty tank booster heater overload protector (OLP). Faulty indoor unit PCB (main). Abnormality Judgment: Continue for 60 seconds.
Page 101
16.5.15 Unspecified Voltage between Indoor and Outdoor (H95) Malfunction Decision Conditions: The supply power is detected for its requirement by the indoor/outdoor transmission. Malfunction Caused: Insufficient power supply. Faulty outdoor unit PCB (noise filter/main).
Page 102
16.5.16 Outdoor High Pressure Protection (H98) Malfunction Decision Conditions: During operation of heating, when pressure 4.0 MPa and above is detected by outdoor high pressure sensor. Malfunction Caused: Faulty water pump. Insufficient water flow rate in system. Water leak in system. 3 way closed.
Page 103
16.5.17 Indoor Freeze-up Protection (H99) Malfunction Decision Conditions: During anti-freezing control in cooling operation, when the indoor refrigerant liquid temperature < 0°C. Malfunction Caused: Faulty water pump. Insufficient water flow rate in system. Water leak in system. 2 way valve partially closed. Clogged expansion valve or strainer.
Page 104
16.5.18 Outdoor High Pressure Switch Activate (F12) Malfunction Decision Conditions: During operation of heating, when pressure 4.5MPa and above is detected by outdoor high pressure switch. Malfunction Caused: Faulty water pump. Insufficient water flow rate in system. Water leak in system. 3 way valve closed.
Page 105
16.5.19 Compressor Rotation Failure (F14) Malfunction Decision Conditions: A compressor rotation failure is detected by checking the compressor running condition through the position detection circuit. Malfunction Caused: Compressor terminal disconnect. Faulty outdoor unit PCB (main). Faulty compressor. Abnormality Judgment: Continue 4 times in 20 minutes.
Page 106
16.5.20 Outdoor Fan Motor (DC Motor) Mechanism Locked (F15) Malfunction Decision Conditions: The rotation speed detected by the Hall IC of the fan motor during fan motor operation is used to determine abnormal fan motor (feedback of rotation > 2550rpm or < 50rpm). Malfunction Caused: Operation stop due to short circuit inside the fan motor winding.
Page 107
16.5.21 Input Over Current Detection (F16) Malfunction Decision Conditions: During operation of heating, when outdoor current above 28.7A is detected by the current transformer (CT) in the outdoor unit PCB. Malfunction Caused: Excessive refrigerant. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 3 times in 20 minutes.
Page 108
16.5.22 Compressor Overheating (F20) Malfunction Decision Conditions: During operation of heating, when temperature above 112°C is detected by the compressor tank temperature sensor. Malfunction Caused: Faulty compressor tank temperature sensor. 3 way valve closed. Refrigerant shortage (refrigerant leakage). Clogged expansion valve or strainer. Faulty outdoor unit PCB (main).
Page 109
16.5.23 IPM Overheating (F22) Malfunction Decision Conditions: During operation of heating, when temperature 95°C is detected by the outdoor IPM temperature sensor. Malfunction Caused: Faulty outdoor unit fan motor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue 3 times in 30 minutes.
Page 110
16.5.24 Output Over Current Detection (F23) Malfunction Decision Conditions: During operation of heating, when outdoor DC current is above 54A is detected by the IPM DC Peak sensing circuitry in the outdoor unit PCB (main). Malfunction Caused: Faulty outdoor unit PCB (main). Faulty compressor.
Page 111
16.5.25 Refrigeration Cycle Abnormality (F24) Malfunction Decision Conditions: During operation of heating, compressor frequency > Frated. During operation of heating, running current: 0.65A < I < 1.65A. During operation of heating, indoor refrigerant liquid temperature - water inlet temperature < 5°C. Malfunction Caused: Faulty water inlet or indoor refrigerant liquid temperature sensors.
Page 112
16.5.26 Four Way Valve Abnormality (F25) Malfunction Decision Conditions: During heating operation, when the indoor pipe temperature of thermostat ON indoor unit < 0°C. Malfunction Caused: Faulty sensor. Faulty connector connection. Faulty outdoor unit PCB (noise filter/main). Faulty four way valve. Abnormality Judgment: Continue 4 times in 30 minutes.
Page 113
16.5.27 Outdoor High Pressure Switch Abnormal (F27) Malfunction Decision Conditions: During compressor stop, and outdoor high pressure switch is remain opened. Malfunction Caused: Faulty connector connection. Faulty switch. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue for 1 minute.
Page 114
16.5.28 Indoor Water Outlet Temperature Sensor 2 Abnormality (F30) Malfunction Decision Conditions: During startup and operation of cooling and heating, the temperatures detected by the indoor water outlet temperature sensor 2 are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor.
Page 115
16.5.29 Outdoor Air Temperature Sensor Abnormality (F36) Malfunction Decision Conditions: During startup and operation of heating, the temperatures detected by the outdoor air temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue for 5 seconds.
Page 116
16.5.30 Indoor Water Inlet Temperature Sensor Abnormality (F37) Malfunction Decision Conditions: During startup and operation of heating, the temperatures detected by the indoor water inlet temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty indoor unit PCB (main).
Page 117
16.5.31 Outdoor Discharge Pipe Temperature Sensor Abnormality (F40) Malfunction Decision Conditions: During startup and operation of heating, the temperatures detected by the outdoor discharge pipe temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main).
Page 118
16.5.32 Power Factor Correction (PFC) Abnormality (F41) Malfunction Decision Conditions: During operation of heating, when the PFC protection circuitry in the outdoor unit PCB (main) senses abnormal high DC voltage level. Malfunction Caused: Power supply surge. Compressor windings not uniform. Faulty outdoor unit PCB (main).
Page 119
16.5.33 Outdoor Pipe Temperature Sensor Abnormality (F42) Malfunction Decision Conditions: During startup and operation of heating, the temperatures detected by the outdoor pipe temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue for 5 seconds.
Page 120
16.5.34 Outdoor Defrost Temperature Sensor Abnormality (F43) Malfunction Decision Conditions: During startup and operation of heating, the temperatures detected by the outdoor defrost temperature sensor are used to determine sensor error. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty outdoor unit PCB (main). Abnormality Judgment: Continue for 5 seconds.
Page 121
16.5.35 Indoor Water Outlet Temperature Sensor Abnormality (F45) Malfunction Decision Conditions: During startup and operation of heating, the temperatures detected by the indoor water outlet temperature sensor are used to determine sensor errors. Malfunction Caused: Faulty connector connection. Faulty sensor. Faulty indoor unit PCB (main).
Page 122
16.5.36 Outdoor Current Transformer Open Circuit (F46) Malfunction Decision Conditions: A current transformer (CT) open circuit is detected by checking the compressor running frequency (≥ rated frequency) and CT detected input current (< 0.65A) for continuously 20 seconds. Malfunction Caused: CT defective.
Page 123
16.5.37 Cooling High Pressure Overload Protection (F95) Malfunction Decision Conditions: During operation of cooling, when pressure 4.0MPa and above is detected by outdoor high pressure sensor. Malfunction Caused: Dust accumulation in the outdoor unit heat exchanger. Air short circuit at outdoor unit. 2 way valve closed.
17. Disassembly and Assembly Instructions WARNING High Voltage are generated in the electrical parts area by the capacitor. Ensure that the capacitor has discharged sufficiently before proceeding with repair work. Failure to heed this caution may result in electric shocks. 17.1 To Remove Front Plate Please follow the steps below for take out front plate.
17.3 To Remove Pressure Gauge Pressure Gauge 1. Remove 3 screws then use spanner to release nut of Pressure Gauge. 17.4 To Remove Control Panel 1. Disconnect the connector Control Panel of CN-REMOTE2 (WHT) from the Electronic Controller Board. Electronic Controller Board 2.
17.5 To Remove RCCB 1. Disconnect 2 lead wires 2. Disconnect 2 lead wires (Black and White). (Black and White). 3. Remove screws to remove RCCB. RCCB...
17.6 To Remove Transformer and Electronic Controller Board Transformer 4. Remove screw to remove 2. Remove 3 screws to the Electronic Control Board. remove Transformer. Electronic Controller Board CN-T1 1. Disconnect the 2 lead wire 3. Disconnect all connectors, T1, T2 (Black) and connector CN-PWR (BLK), SN-SOLAR (WHT), CN-T1 (WHT) from the CN-PUMP2 (WHT), CN-V2 (WHT),...
During reinstall Air Purge Valve. Make sure plug is fully close in clockwise direction. Apply some water based grease on packing surface Packing before fix with shut off valve. 17.8 To Remove Water Pump and Bottle Complete 2. Loosen the nut. 3.
Page 129
4. Disconnect the connector of CN-OLP1 and lead wire HT1-L1, HT1-L2 and HT1-L3. 5. Loosen 3 nuts. Bottle Complete 6. Remove 4 screws to remove the Bottle Complete. When reinstall the water pipe, use grease or water at the joining.
18. Technical Data 18.1 Operation Characteristics 18.1.1 WH-SHF09F3E5 WH-UH09FE5 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 13.000...
Page 131
Heating Characteristics at Different Piping Length Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 10.000 9.000 8.000 7.000 6.000 5.000 Piping Length (m) 3.000 2.500 2.000...
Page 132
18.1.2 WH-SHF12F6E5 WH-UH12FE5 Heating Characteristics at Different Outdoor Air Temperature Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 15.000 14.000 13.000 12.000 11.000 10.000 Outdoor Temperature (°C)
Page 133
Heating Characteristics at Different Piping Length Condition Outdoor air temperature : 7°C (DBT), 6°C (WBT) Indoor water inlet temperature : 30°C Indoor water outlet temperature : 35°C Piping length : 7 m 13.000 12.000 11.000 10.000 9.000 8.000 Piping Length (m) 4.000 3.500 3.000...
18.2 Heating Capacity Table 18.2.1 WH-UH09FE5 Water Out (°C) Input Input Input Input Input Input Capacity Capacity Capacity Capacity Capacity Capacity Outdoor Air (°C) Power Power Power Power Power Power 9000 3460 9000 3710 9000 4010 8800 4260 8600 4610 8500 4910 9000...
19. Exploded View and Replacement Parts List 19.1 WH-SHF09F3E5 WH-SHF12F6E5 Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 137
< Model: WH-SHF09F3E5 WH-SHF12F6E5> SAFETY REF. NO. DESCRIPTION & NAME QTY. WH-SHF09F3E5 WH-SHF12F6E5 REMARK BASE PAN CWD521266 ← HOT WATER COIL - COMPLETE CWB90C1088 ← RECEIVER CWB141039 ← FLOW SWITCH CWB621128 ← FLARE NUT (28 mm) CWT251064 ← FLARE NUT (22 mm) CWT251061 ←...
Page 140
Note: The above exploded view is for the purpose of parts disassembly and replacement. The non-numbered parts are not kept as standard service parts.
Page 141
< Model: WH-UH09FE5 WH-UH12FE5> SAFETY REF. NO. DESCRIPTION & NAME QTY. WH-UH09FE5 WH-UH12FE5 REMARK BASE PAN ASS’Y CWD52K1275 ← COMPRESSOR 4JD650XAA22 ← BUSHING - COMPRESSOR MOUNT CWH50055 ← NUT - COMPRESSOR MOUNT CWH561049 ← GASKET FOR TERMINAL COVER CWB811017 ← CRANKCASE HEATER CWA341053 ←...