Panasonic OCU-CR200VF5 Operating Instructions And Installation Instructions page 15

Outdoor type refrigeration unit
Hide thumbs Also See for OCU-CR200VF5:
Table of Contents

Advertisement

Carry-in / Installation
Foundation / Platform Work
● As a reference, the foundation should be made from concrete having a mass about 3 times that of the
refrigeration unit. (Absorbing vibration by mass)
● Vibration should be reduced by a platform or anti-vibration pad for avoiding transmission of vibration to the fl oor
and wall.
● To avoid falling, secure the refrigeration unit by using anchor bolts. (Use all securing positions)
● The refrigeration unit must be installed with an inclination angle 1° or below.
● The refrigeration unit must be installed below the altitude of 2000 m.
If a foundation meeting the requirement above cannot be secured, be sure to check that no abnormal vibration is
generated by resonation of the refrigeration unit and piping system.
(1) Standard foundation work
On a concrete foundation 150 mm or higher from the fl oor surface, place anti-vibration pads (Approx. 8 to 15 mm
thick) and secure the unit on the entire unit base by anchor bolts.
(2) When using angles
Secure angles on a fi rm concrete foundation by using anchor bolts.
(3) Anchor bolts
Use M8 size anchor bolts and buried at least 100 mm on the concrete foundation.
Fix unit with double nut and plain washer (28 mm O.D. minimum).
External Dimensions
(133)
600(Installation pitch)
13
4-Ø13(Round cutout)
13
Power supply hole(Ø26)
Power supply hole(Ø38)
Refrigerant piping hole
Optional Accessories
The following service piping (optional) is required for the installation and
service work of the refrigeration unit.
Service piping for Evacuation, Airtight test, and Refrigerant charging (Model
No. SPK-TU125)
167
13
13
900
Suction
(Ø9.52 inner diameter
connection)
Liquid
(Ø6.35 inner diameter
connection)
52 49
81
22
47
Power supply hole(Ø26)
Power supply hole(Ø38)
Refrigerant piping hole
20
55
A section Enlarged View
437
320
Air
Air
56 52
A
29
81
EN - 15
Power supply hole(Ø38)
Power supply hole(Ø26)
Refrigerant piping hole
Connected to the unit service valve
Nut (fastening torque 13 ± 1 N·m)

Advertisement