Installation Instruction; Select The Best Location; How To Fix Installation Plate - Panasonic WH-SDC12H9E8 Service Manual

Air-to-water heatpump
Hide thumbs Also See for WH-SDC12H9E8:
Table of Contents

Advertisement

Installation Instruction

Indoor Unit

Select the Best Location

There should not be any heat source or steam
near the unit.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into
consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the
wall, ceiling, fence or other obstacles.
Recommended installation height for indoor unit
shall be at least 800 mm.
Must install on a vertical wall.
When install electrical equipment at wooden
building of metal lath or wire lath, according to
electrical facility technical standard, no electrical
contact between equipment and building is
allowed. Insulator must be installed in between.
Do not install the unit at outdoor. This is designed
for indoor installation only.
Required space for installation
100 mm
or more

How To Fix Installation Plate

The mounting wall is strong and solid enough to
prevent it from vibration.
More than 375 More than 375
Wall
5
≥1556 from
ground
70
160
100 mm
or more
100 mm
or more
(Unit in mm)
Wall
5
Installation
plate 1
Indoor Unit
body
Bolt -
size M8
Installation
200
plate 4
The centre of installation plate should be at more than
375 mm at right and left of the wall.
The distance from installation plate edge to ground
should more than 1556 mm.
Always mount the installation plate horizontally
plate by aligning the marking thread and using a
level gauge.
Mount the installation plate on the wall with 6 sets
of plug, bolt and washer (all non-supply) with size
M8.
To Drill A Hole In The Wall And
Install A Sleeve Of Piping
1. Insert the piping sleeve to the hole.
2. Fix the bushing to the sleeve.
3. Cut the sleeve until it extrudes about 15 mm
from the wall.
When the wall is hollow, please be sure to use the sleeve
for tube assembly to prevent dangers caused by mice
biting the connection cable.
4. Finish by sealing the sleeve with putty or
caulking compound at the final stage.
Wall
Indoor
Sleeve for tube
assembly
ø70 mm through hole
Indoor Unit Installation
Access to Internal Components
This section is for authorized and licensed electrician/water
system installer only. Work behind the front plate secured by
screws must only be carried out under supervision of qualified
contractor, installation engineer or service person.
Please follow the steps below for take out front plate.
Before removing the front plate of indoor unit, always
switch off all power supply (i.e. indoor unit power
supply, heater power supply and Tank Unit power
supply).
1. Remove the 2 mounting screws which located at
bottom of the front plate.
CAUTION
Outdoor
15 mm
Approx. 5 - 7 mm
Bushing for tube assembly
Putty or caulking compound
WARNING