Troubleshooting
Configuration problems (continued)
Description
Not able to store /
Incorrect signature.
restore parameters.
Non-volatile memory error.
When the Unit detects a non-volatile memory
error, an emergency message is transmitted
(see section 6-2) and error code 05h will be
blinking on the 7-segment display.
I/O data communication problems
Description
7-segment display
The 7-segment display indicates the cause.
value is Blinking.
Refer to section 6-5 for a list with error codes.
7-segment display
The Unit is in 'Pre-Operational' state.
dots are ON.
Also indicated by IR n+3.00 and IR n+3.01.
7-segment display
The Unit is in 'Stopped' state.
dots are Blinking.
Also indicated by IR n+3.00 and IR n+3.01.
No
I/O
data
is
The network cabling is not correct.
exchanged with the
PLC although the
RUN LED is ON.
7-segment
display
value is not Blinking
The Unit operates on a different baud rate than
and the dots are
the other units on the network.
OFF.
The CANopen communication is disabled.
IR n.00 is not set. Display value is FFh.
Application object(s) not mapped to a PDO.
PDO is not enabled.
Wrong transmission type
Application object(s) not mapped to a PLC
address. If an application object is not mapped
to a PLC address, it might appear that the Unit
is not communicating.
100
Possible cause
Possible cause
Possible remedy
To store parameters, the signature 'save' has
to be written to sub-index 01h of index 1010h.
To restore parameters, the signature 'load'
has to be written to sub-index 01h of index
1011h.
See section 3-3-2-9 for details.
Try to store the configuration again and / or
restart the Unit. Note that storing the
configuration takes approx. four seconds; the
Unit should not be reset in this period.
If the error keeps occurring, replace the Unit.
Possible remedy
Try to solve the cause and/or restart the Unit.
If this does not help, replace the Unit.
Send
the
NMT
'Start_Remote_Node' to the Unit or set IR
n.01. The Unit should go to Operational state
and the dots should go OFF.
Send
the
NMT
'Start_Remote_Node' to the Unit or set IR
n.01. The Unit should go to Operational state
and the dots should go OFF.
Check if the correct pins of the bus connector
are connected (see section 3-1-5), if there are
no short circuits, if the stub-lines are not too
long, and if the network is terminated at the
appropriate places (see section 3-3-1).
Configure all the units on the network to the
same baud rate.
Set IR n.00 ON.
Configure the desired application object(s) to
a PDO and configure the communication
parameters of that PDO (see section 3-3-2-1
and section 3-3-2-2).
The highest bit of the COB-ID (sub-index 01h
of the PDO Communication Parameters)
determines whether the PDO is valid or not.
Normally, the configuration tool enables the
PDO (by clearing this bit) when the application
object
mapped to the respective PDO is
linked to another Unit. Check if this bit is
cleared and if not, clear it manually.
Set the correct transmission type. See section
3-3-2-1 for the possible transmission modes.
Configure the Unit settings to map the desired
application object(s) to a PLC address.
Section 7-2
command
command