6.2
% of Load Bar
6–4
The 10-segment LED bargraph at the bottom of the EPM2200 unit's display provides a
graphic representation of Amps. The segments light according to the load in the %Load
Segment Table below.
When the Load is over 120% of Full Load, all segments flash "On" (1.5 secs) and "Off" (0.5
secs).
Segments
None
1
1 - 2
1 - 3
1 - 4
1 - 5
1 - 6
1 - 7
1 - 8
1 - 9
1 - 10
All Blink
Table 6–1: % Load Segments
Load ≤ % Full Load
No Load
1%
15%
30%
45%
60%
72%
84%
96%
108%
120%
>120%
EPM 2200 MULTI-FUNCTION POWER METERING SYSTEM – USER GUIDE
CHAPTER 6: USING THE METER