M-system R9MWTU Instruction Manual page 3

Multi power monitoring unit (clamp-on current sensor clse, modbus)
Table of Contents

Advertisement

■ OPERATING MODE SETTING
(*) Factory setting
• System Configuration (SW1-1, 2)
SW1-1
SW1-2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
• Balanced or Unbalanced Load (SW1-3)
SW1-3
OFF
ON
• Clamp Sensor Type (SW1-4, 5, 6)
SW1-4
SW1-5
SW1-6
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
OFF
OFF
ON
ON
ON
OFF
OFF
ON
ON
■ TERMINAL ASSIGNMENTS
• Modbus
3
2
1
FE
SLD
DB
7
6
5
NC
NC
DG
DA
No.
ID
FUNCTION
1
DB
DB
2
SLD
Shield
3
FE
Modbus ground
4
DA
DA
5
DG
DG
6
NC
Unused
7
NC
Unused
• Auxiliary Power Supply, Voltage Input
4
5
6
P1
P2
P3
1
2
3
U(+)
V(−)
FE1
No.
ID
FUNCTION
1
U(+)
Auxiliary power (+)
2
V(−)
Auxiliary power (−)
3
FE1
Power ground
4
P1
Voltage input P1
5
P2
Voltage input P2
6
P3
Voltage input P3
7
N
Voltage input N
SYSTEM CONFIGURATION
Three-phase / 3-wire (*)
Single-phase / 2-wire
Single-phase / 3-wire
---
BALANCED / UNBALANCED
Unbalanced (*)
Balanced
CLAMP SENSOR TYPE
CLSE-R5 (5A) (*)
CLSE-05 (50A)
CLSE-10 (100A)
CLSE-20 (200A)
CLSE-40 (400A)
CLSE-60 (600A)
• Current Input 2
4
No.
1
2
3
4
5
6
7
8
9
• Current Input 1
7
N
No.
1
2
3
4
5
6
7
8
9
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
• Configuration Mode (SW1-8)
SW1-8
CONFIGURATION MODE
OFF
DIP switch setting (*)
(PC Configurator setting is invalid.)
ON
PC Configurator and communication
(DIP switch setting is invalid.)
Note 1: Turn on the power supply to the unit after setting node
address, baud rate and operating mode.
Note 2: Be sure to set unused SW1-7 to OFF.
Note 3: Clamp sensor type setting is common to all circuits.
Note 4: The sensor type and other settings for individual
circuit can be performed on the PC Configurator or via
Modbus.
9
8ch
8
8ch
7
7ch
6
7ch
5
T2
3L
1L
3L
1L
18
8ch
17
8ch
16
7ch
15
7ch
14
6ch
T1
3K
1K
3K
1K
3K
ID
FUNCTION
5ch 1L Ch.5, Current input 1L
5ch 3L Ch.5, Current input 3L
6ch 1L Ch.6, Current input 1L
6ch 3L Ch.6, Current input 3L
7ch 1L Ch.7, Current input 1L
7ch 3L Ch.7, Current input 3L
8ch 1L Ch.8, Current input 1L
8ch 3L Ch.8, Current input 3L
T2
Unused
10
1ch
11
1ch
12
2ch
13
2ch
14
NC
1K
3K
1K
3K
1
1ch
2
1ch
3
2ch
4
2ch
5
3ch
NC
1L
3L
1L
3L
1L
ID
FUNCTION
NC
Unused
1ch 1L Ch.1, Current input 1L
1ch 3L Ch.1, Current input 3L
2ch 1L Ch.2, Current input 1L
2ch 3L Ch.2, Current input 3L
3ch 1L Ch.3, Current input 1L
3ch 3L Ch.3, Current input 3L
4ch 1L Ch.4, Current input 1L
4ch 3L Ch.4, Current input 3L
R9MWTU
6ch
4
6ch
3
5ch
2
5ch
1
3L
1L
3L
1L
13
6ch
12
5ch
11
5ch
10
1K
3K
1K
No.
ID
FUNCTION
10
5ch 1K Ch.5, Current input 1K
11
5ch 3K Ch.5, Current input 3K
12
6ch 1K Ch.6, Current input 1K
13
6ch 3K Ch.6, Current input 3K
14
7ch 1K Ch.7, Current input 1K
15
7ch 3K Ch.7, Current input 3K
16
8ch 1K Ch.8, Current input 1K
17
8ch 3K Ch.8, Current input 3K
18
T1
Unused
3ch
15
3ch
16
4ch
17
4ch
18
1K
3K
1K
3K
6
3ch
7
4ch
8
4ch
9
3L
1L
3L
No.
ID
FUNCTION
10
NC
Unused
11
1ch 1K Ch.1, Current input 1K
12
1ch 3K Ch.1, Current input 3K
13
2ch 1K Ch.2, Current input 1K
14
2ch 3K Ch.2, Current input 3K
15
3ch 1K Ch.3, Current input 1K
16
3ch 3K Ch.3, Current input 3K
17
4ch 1K Ch.4, Current input 1K
18
4ch 3K Ch.4, Current input 3K
EM-6221 Rev.9 P. 3 / 20

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the R9MWTU and is the answer not in the manual?

Table of Contents