INSTRUCTION MANUAL
THERMOCOUPLE & DC INPUT MODULE
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
This product is for use in general industrial environments,
therefore may not be suitable for applications which require
higher level of safety (e.g. safety or accident prevention sys-
tems) or of reliability (e.g. vehicle control or combustion con-
trol systems).
For safety, installation and maintenance of this product
must be conducted by qualified personnel.
■ PACKAGE INCLUDES:
Remote I/O module .............................................................(1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
For detailed information on Modbus supported functions,
refer to Modbus Protocol Reference Guide (EM-5650).
The R1M is programmable using the PC configurator soft-
ware. For detailed information on the PC configuration,
refer to the R1CON instruction manual. The R1CON PC
Configurator Software is downloadable at M-System's web
site: http://www.m-system.co.jp.
(8 points; isolated)
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
MODEL
POINTS OF CAUTION
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 240V AC rating: 85 – 264V, 47 – 66 Hz, approx. 9VA
24V DC rating: 24V ±10%, approx. 3.5W
■ GENERAL PRECAUTIONS
• Before you remove the module, turn off the power supply,
input signal and output signal for safety.
■ ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the air,
install the module inside proper housing with sufficient
ventilation.
• Do not install the module where it is subjected to continu-
ous vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +60°C
(23 to 140°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
• Be sure that the ventilation slits are not covered with ca-
bles, etc.
• Sudden ambient temperature change could increase the
cold junction compensation error by the internal terminal
temperature sensor. Stabilize the temperature around
the terminal block.
■ WIRING
• Wrong connection may damage the module.
• Do not connect cables to moving parts or pull them tightly.
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■ AND ....
• The module is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required
for satisfying complete performance described in the data
sheet.
R1MS-GH3
EM-5671 Rev.6 P. 1 / 8

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the R1MS-GH3 and is the answer not in the manual?

Questions and answers

Summary of Contents for M-system R1MS-GH3

  • Page 1 (8 points; isolated) BEFORE USE ..POINTS OF CAUTION Thank you for choosing M-System. Before use, please check ■ POWER INPUT RATING & OPERATIONAL RANGE contents of the package you received as outlined below. • Locate the power input rating marked on the product and...
  • Page 2: Component Identification

    19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 35 3 (.12) 163 (6.42) [6 (.24)] 40 (1.57) FOR WALL MOUNT. 6.2 (.24) 36–M3 I/O TERMINALS EM-5671 Rev.6 P. 2 / 8 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 3 AB (SG) Signal Common CB (CS) Clear to Send CA (RS) Request to Send Not Used. DO NOT connect. Connecting may cause malfunctions. EM-5671 Rev.6 P. 3 / 8 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 4: Wiring Instructions

    *1. Internal terminating resistor is used when the device is at the end of a transmission line. *2. Install shielded cables to all sections and ground them at single point. EM-5671 Rev.6 P. 4 / 8 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 5: Modbus Communication

    Slave type / ‘RUN’ status Program 884/M84 Reset Comm. Link Read General Reference Write General Reference Mask Write 4X Register Read/Write 4X Register Read FIFO Queue EM-5671 Rev.6 P. 5 / 8 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 6 Line noise filtering type (0: 50/60 Hz, 1: 50 Hz, 2: 60 Hz) * bit =1bit, I = 16-bit integer, F = 32-bit floating, B16 = 16-byte character *1. Changeable only when the mode SW is set to 0 for R1MS-GH3. *2. Thermocouple input only.
  • Page 7 0x42 0 to 1 kohms 0 to 100 % 0x43 0 to 10 kohms 0 to 100 % R1M-D1 0x60 R1M-A1 0x70 EM-5671 Rev.6 P. 7 / 8 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...
  • Page 8: Adjustment Procedure

    50%, 75% and 100% input signal. Check that the output signal for the respective input signal remains within accu- racy described in the data sheet. When the output is out of tolerance, please contact M-System’s Sales Office or repre- sentatives. EM-5671 Rev.6 P. 8 / 8 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp...