SLM50 suspended vertical ladders for the maintenance of electrical function

Fastening cables

Function loss through excessive cable load!
At an excessive cable load, the perfect functioning of the vertical ladder
cannot be guaranteed in the event of fire. Observe the maximum cable
load and specifications for the cable assignment.
– Cable load per vertical ladder max. 20 kg/m
– Cable bundling, heavy current cables, max. quantity 3, max. diameter
25 mm
– Cable bundling, installation cables, quantity not limited, total cable
weight max. 3.0 kg/m
Fig 37: Fastening cables
1. Fasten cables to the ladder rungs with clamp clips, type 2056U M.

Attaching the identification plate

The cable system must be given an identification plate, in accordance
with DIN 4102 Part 12.
1. Clearly fill out the KS-E identification plate with a permanent marker.
2. Stick the KS-E identification plate to the ladder rail of the suspended
vertical ladder.