SLM50 suspended vertical ladders for the maintenance of electrical function

Mounting vertical ladders up to a max storey height of 3 5 m

Mounting vertical ladders up to a max storey height of 3 5 m
Function loss in the event of fire!
At a storey height > 3.5 m, perfect functioning of the vertical ladder can-
not be guaranteed in the event of fire. Only use mounting variants at a
storey height of maximum 3.5 m.

Mounting the ladder rails with head plates

Fig 3: Drawing on the drill holes
Distance "a" is dependent on the width of the vertical ladder used. a =
vertical ladder width – 50 mm.
1. Draw on two drill holes at spacing "a" behind the ceiling opening.
Maintain the minimum edge spacing according to the approval of the
anchor used.
2. Using a linear laser, transfer the position of the drill holes to the floor.
3. Pre-drill the drill holes. Ø according to anchor type and approval.
Fig 4: Mounting head plates
4. Mount head plates with the open sides facing each other, using one
M12 anchor for the ceiling and one for the floor.