Mounting U Support Connectors - OBO Bettermann SLM50 Mounting Instructions

Table of Contents

Advertisement

Mounting U support connectors

6 5
Note!
30 | EN
Mounting U support connectors
The U support connector can connect two vertical ladder rails, in order to
connect storey heights > 3.0 m.
Fig 36: Mounting U support connectors
1. Mount each of the U support connectors with 3 M10 truss-head bolts
to the ladder rails already mounted under the ceiling.
– Mount the connectors with the opening pointing inwards.
– Place the bolts up to the limit in the slot, in order to prevent a verti-
cal movement of the connector.
2. Mount each additional ladder rail to the U support connectors with 3
truss-head bolts.
– Mount the rails with the opening pointing inwards.
– Place the bolts up to the limit in the slot, in order to prevent a verti-
cal movement of the vertical ladders.
The maximum distance between the ladder rungs above and below the
U support connector is 300 mm.
OBO Bettermann