2.3.1 G5 Power/Signal Connections
1. Input power requirements:
• 24 VAC (20 - 28 VAC), 16 - 90 VA, varies based on number of
sensors.
• 24 VDC (20 - 28 VDC), 16 - 50 W, varies based on number of
sensors.
2. Alarm can be set for either flow or temperature with upper and
lower limits. Refer to page 16 for more information.
2.3.2 G5 Analog Outputs and Serial Communication
TB - J1
AO OUT 1 & 2
IMPORTANT NOTE
Two (2) analog outputs (4 - 20 mA, 0 - 10 VDC or 0 - 5 VDC) are
available based on configuration. Refer to page 15 for more
information.
3/21 IOM-ELECTRA-FLO-INST
Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
S1
TERM
BIAS
24 V INPUT PWR
AO1 / AO2
BACnet
ALARM
+ COM / + COM
D+ D- G SH
NO C NC
L
J1
J2
J3
TB - J3
ALARM
CONNECTION
NORMALLY CLOSED CONTACT (NC)
COMMON (C)
NORMALLY OPEN CONTACT (NO)
S1
TERM
BIAS
AO1 / AO2
BACnet
ALARM
+ COM / + COM
D+ D- G SH
NO C NC
J1
J2
J3
(-) AO2 COMMON
(+) AO2
(-) AO1 COMMON
(+) AO1
N
G
J4
TB - J4
INPUT POWER
2
24 V INPUT PWR
L
N
G
J4
TB - J2
SERIAL
COMMUNICATION
1
GROUND (G)
(-) COMMON (N)
(+) 24 V AC/DC (L)
SHIELD (SH)
RS485 COMMON (G)
(-) RS485 (D)
(+) RS485 (D)