Nailor ELECTRA-FLO G5 Operation And Maintenance Manual page 27

Thermal airflow & temperature measurement system. airflow transmitter for models amd-td-10 & amd-td-20
Table of Contents

Advertisement

INPUT REGISTERS FOR SYSTEM VARIABLES
DESCRIPTION
System Velocity Units
System Flow Units
Version
System Status 1
System Node Total 1
Duct Shape 1
Design Flow Max 1 Setting
Duct Area 1
System Status 2
System Node Total 2
Duct Shape 2
Design Flow Max 2 Setting
Duct Area 2
DISCREET INPUTS FOR SYSTEM VARIABLES
DESCRIPTION
Sensor Enabled
Sensor Enabled
System Units
System Conditions
Rules for Discrete Inputs (2x)
Up to 32 Registers can be requested from 20000 addresses or 20002 addresses.
Any other address returns "Illegal Address"
No more than 32 registers can be requested. Anymore than 32 will return "Illegal Address"
System Conditions has a maximum of (2) registers from the base address 20004
COILS FOR SYSTEM VARIABLES
DESCRIPTION
K-factor 1
K-factor 2
System Reset
K-factor 1
K-factor 2
DESCRIPTION
report slave ID
3/21 IOM-ELECTRA-FLO-INST
Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
ADDRESS
DATA TYPE
30400
uint16_t
30401
uint16_t
30402
uint16_t
30403
uint16_t
30404
uint16_t
30405
uint16_t
30406
uint16_t
30407
float
30408
float
30409
uint16_t
30410
uint16_t
30411
uint16_t
30412
float
30413
float
ADDRESS
DATA TYPE
10000
boolean
10001
boolean
10002
boolean
10002
boolean
ADDRESS
DATA TYPE
00001
boolean
00002
boolean
00003
boolean
00004
boolean
00005
boolean
ADDRESS
DATA TYPE
17
ASCII
DESCRIPTION
1 = FPM, 2 = FPS, 3 = MPM, 4 = MPS
1 = CFM, 2 = CFH, 3 = L/S, 4 = L/M, 5 = M3H
MSB = Major, LSB = Minor
MSB = Patch, LSB = Build Number
1 = ALL_OK, 2 = IN ALARM, 3 = IN FAULT, 4 = 00S
1 = 32 NODES ALLOWED
1 = Rect, 2 = Round, 3 = FLAT OVAL
Max Flow to scale Analog Outputs
Duct area size in ft
2
or m
2
1 = ALL_OK, 2 = IN ALARM, 3 = IN FAULT, 4 = 00S
1 = 32 NODES ALLOWED
1 = Rect, 2 = Round, 3 = FLAT OVAL
Max Flow to scale Analog Outputs
Duct area size in ft
2
or m
2
DESCRIPTION
Bit0-Bit15 Sensor Enabled
Bit16-Bit31 Sensor Enabled
Coil 1: 1 = Sl, Bit 0: 0 = US
Coil 2: 1 = Std, Bit 0: 0 = Actual
DESCRIPTION
1 = ON, 0 = OFF
1 = ON, 0 = OFF
1 = RESET
Returns the state of the K-factor
Returns the state of the K-factor
DESCRIPTION
Returns string "ELECTRA-flo G5"
Page 27