Main Menu - Nailor ELECTRA-FLO G5 Operation And Maintenance Manual

Thermal airflow & temperature measurement system. airflow transmitter for models amd-td-10 & amd-td-20
Table of Contents

Advertisement

Service Menu System 1 and System 2 (Dual Channel Version Only)
Service Menu Selection
Password Configuration
Total System Scan
Sensor Enable/Disable
Sensor Data Scan
Sensor Alert Scan
Custom ID
Restore Factory Setting
Product Information
Configure Probes vs. Nodes
Network Configuration
Network Configuration

3.3 MAIN MENU

DENSITY COMPENSATION
CONDITIONS:
SITE ELEVATION:
ENT - ACCEPT ESC - DEL/LEAVE UP/DN - CHANGE
SYSTEM OF UNITS
SYSTEM:
ENT - ACCEPT ESC - DEL/LEAVE UP/DN - CHANGE
UNITS OF MEASURE
TEMPERATURE
VELOCITY
FLOW:
ENT - ACCEPT ESC - DEL/LEAVE UP/DN - CHANGE
3/21 IOM-ELECTRA-FLO-INST
Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
Enable/disable and change password
Displays sensor enabled/disabled status
Enable or disable system sensors
Displays individual sensor data
Displays alert codes for each sensor
Configure ID (tag) of unit (also device name displayed in BACnet)
Restores display settings to original factory setup
Displays product information (Serial number, Work Order #, etc.)
Configure number of probes and sensors per probe
Configure BACnet MS/TP or MODBUS RTU Network Connection
STANDARD
0
US
DEG F
SCFM
SFPM
SCFM
Description
Description
Density Compensation - Density compensation can be
selected to be actual flow or flow corrected to standard
conditions. The default factory setting is for actual conditions.
The Airflow G5 also allows for inputting the site elevation,
which will add density compensation for average atmospheric
pressure based upon elevation above sea level.
Select System of Units - US or SI units can be selected. US
units will display in CFM and °F. SI units will display in L/s and °C.
IMPORTANT NOTE
When changing between US and SI units, the flow
configuration information will need to be converted and
updated. This is not done by the transmitter. The user must
convert and input.
Select Units of Measure - US and SI velocity and flow units
can be selected.
Page 13