Nailor ELECTRA-FLO G5 Operation And Maintenance Manual page 5

Thermal airflow & temperature measurement system. airflow transmitter for models amd-td-10 & amd-td-20
Table of Contents

Advertisement

1.3 Standard Features and Specifications - continued*
ELECTRA-flo/S5 Thermal Dispersion Probe Array - continued
Duct & Station
Sensor
Mounted
Density
Fan Inlet
Probe
Available
Materials of
Options
Construction
Fluid Temperature
Operating
Conditions
Humidity
Wiring
Available
Options
Connections
Duct Mounted
Mounting
Probe Arrays
Options
Options
1
NOTE:
Field characterization required to achieve ±3% system accuracy.
* SPECIFICATIONS subject to change without notice.
3/21 IOM-ELECTRA-FLO-INST
Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
Three (3) sensor density levels specifiable based on configuration
Single or dual sensor configuration per inlet available
• 6063 anodized aluminum, 1 1/8" diameter with NEMA 1 enclosure
• 6063 anodized aluminum, 1 1/8" diameter with NEMA 4 enclosure and IP67
connectors
• 6063 anodized aluminum, 1 1/8" diameter with NEMA 4 enclosure and 1/2" (13)
conduit connections
• 300 series stainless steel, 1 1/8" diameter with NEMA 4X enclosure and 1/2" (13)
conduit connections
-20°F to 140°F (-29°C to 60°C)
0 to 99% RH, non-condensing
• Mini-DIN, NEMA 1 only
• Watertight - IP67
• Conduit opening with terminal blocks
• Rectangular duct, external or internally mounted
• Rectangular duct, standoff mount
• Circular duct, external or internally mounted
• Aluminum honeycomb airflow straightening cell
Page 5

Advertisement

Table of Contents
loading