Nailor ELECTRA-FLO G5 Operation And Maintenance Manual page 30

Thermal airflow & temperature measurement system. airflow transmitter for models amd-td-10 & amd-td-20
Table of Contents

Advertisement

Property
Type
Missing
ALERT
SensAOOR or
ALERT
SensBOOR
DeltaOOR
ALERT
TempOOR
RANGE
Disabled
ALERT
VelOOR
RANGE
CUSTOM ID
ID:
CHANGE ID:
ENT - ACCEPT ESC - DEL/LEAVE UP/DN - CHANGE
RESTORE FACTORY SETTINGS
RESTORE:
ENT - ACCEPT ESC - DEL/LEAVE UP/DN - CHANGE
PRODUCT INFORMATION
WO # 90525
SERIAL NUMBER: 0987654321
PART NUMBER: 106-058-00
MODEL: ELECTRA-FLO
DATE OF MFG: 2/1/2020 13:33
HARDWARE VER: 1
FIRMWARE VER: 1.1.0 BUILD 20
NODES: 1 PROBES: 1
Page 30
Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
Description
Transmitter cannot communicate
with Sensor
Sensor fault
Sensor Delta Temperature out of
range
Temperature measurement out of
range (-20 to 140F)
Sensor resets abnormally
Average velocity exceeds 5000
FPM for ducted and 10,000 FPM
for Fan Inlet
CUSTOM ID
YES, SURE?
ESC - LEAVE
Corrective Action
Power cycle sytem and recheck
Replace sensor. Contact Nailor.
Contact Nailor
Verify application temperature is not outside
-20 to 140F. If ELECTRA-flow G5 appears
to be reporting incorrectly, contact Nailor.
Power cycle system and recheck
Verify factory set-up information is correct.
If application velocity exceeds 5000 FPM,
contact Nailor.
Custom ID
This menu page is used to input an alpha-numeric entry of up
to 20 characters.
This entry is visible on the bottom of the main display screen
and is written to the Device Name field in the BACnet device
object.
Restore Factory Settings
This menu page function restores the transmitter to the factory
default settings.
IMPORTANT NOTE
This function will erase all calibration data. DO NOT
use this without first consulting with Nailor service
personnel.
Product Information
This menu page provides information about the Airflow G5
transmitter hardware and firmware. It also includes information
on the number of probes and nodes connected to the transmitter.
3/21 IOM-ELECTRA-FLO-INST
Status Bar
MISSING
DISABLED
Temp value in
red
Temp value in
red
DISABLED
Velocity value
in red