Nailor ELECTRA-FLO G5 Operation And Maintenance Manual page 18

Thermal airflow & temperature measurement system. airflow transmitter for models amd-td-10 & amd-td-20
Table of Contents

Advertisement

PROTOCOL IMPLEMENTATION STATEMENT
BACnet Protocol Revision: 12
Device Profile (Annex L): BACnet Application Specific Controller
(B-ASC)
MS/TP master (Clause 9), baud rate(s): 9600, 19200, 38400,
56700, 76800, 115200
Device Address Binding: No
BBMD Support Registration By Foreign Devices: No
Character Set Supported: ANSI X3.4
BACnet Interoperability Building Blocks Supported (Annex K):
Data Sharing – Read Property-B (DS-RP-B)
Data Sharing – Read Property Multiple-B (DS-RPM-B)
Data Sharing – Write Property-B (DS-WP-B)
Device Management – Dynamic Device Binding-B (DM-DDB-B)
Device Management – Dynamic Object Binding-B (DM-DOB-B)
Device Management – Device Communication Control-B
(DM-DCC-B)
Device Management – Reinitialize Device-B (DM-RD-B)
Page 18
3/21 IOM-ELECTRA-FLO-INST
Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.