Nailor ELECTRA-FLO G5 Operation And Maintenance Manual page 26

Thermal airflow & temperature measurement system. airflow transmitter for models amd-td-10 & amd-td-20
Table of Contents

Advertisement

MODBUS INPUT REGISTERS
DEVICE
Sensor 22
Sensor 23
Sensor 24
Sensor 25
Sensor 26
Sensor 27
Sensor 28
Sensor 29
Sensor 30
Sensor 31
Sensor 32
MODBUS HOLDING REGISTERS
DEVICE
System Flow Plus
System Flow Minus
Page 26
Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.
ELECTRA-FLO G5 DUAL MODBUS REGISTERS
VELOCITY
30288
float
30292
float
30296
float
30300
float
30304
float
30308
float
30312
float
30316
float
30320
float
30324
float
30328
float
FLOW
Address
Data Type
40000
float
40002
float
TEMPERATURE
30290
float
30294
float
30298
float
30302
float
30306
float
30310
float
30314
float
30318
float
30322
float
30326
float
30330
float
The user can pick off any sensor to determine its value within
range:
30000-300132 - System 1 Sensors
30133-300199-Illegal
30200-30332 - System 2 Sensors
30333-30399 - Illegal
30400-30418 System Params
> 30419 Illegal
Ranges are shown above for the Read Input Registers
IMPORTANT NOTE
MODBUS has a PDU limitation of 125 registers, so extracting
the data from a 32-node system requires two transactions.
3/21 IOM-ELECTRA-FLO-INST
UNITS
see Register 30400
see Register 30400
see Register 30400
see Register 30400
see Register 30400
see Register 30400
see Register 30400
see Register 30400
see Register 30400
see Register 30400
see Register 30400
UNITS
see Register 30401
see Register 30401