Assa Abloy Corbin Russwin SE LP10 Series Installation Instructions Manual page 7

Table of Contents

Advertisement

SE LP10
FE6600/BL6600/MP6600 Series Multi-point Lock
Installation Instructions
5
Wiring Diagrams, continued
Typical FE6600/BL6600/MP6600 x SE LP10 Series Multi-point Lock Application
Diagram (12/24VDC Lock)
Reader Electronics Require 12 or 24VDC Power Supply
12/24VDC System
Reader Draw = 150mA @12 or 24VDC
Actuator Draw = 15mA continuous
Total System Draw = 550mA @12VDC / 24VDC
NOTE:
If your lock is configured with End of Line Resistors, reference instruction sheet FM406 for the wiring of
RX & DPS outputs.
For installation assistance contact Corbin Russwin
1-800-543-3658 • techsupport.corbinrusswin@assaabloy.com
Copyright © 2017, 2020 ASSA ABLOY Access and Egress Hardware Group, Inc. All rights reserved. Reproduction in whole
or in part without the express written permission of ASSA ABLOY Access and Egress Hardware Group, Inc. is prohibited.
Standard Application Shown
For Alternative Applications Contact 1-800-810-WIRE (9473)
12 Conductor
QC12 Electric
ElectroLynx Harness
Hinge From
From McKinney
McKinney
FE6600 / BL6600/
MP6600
Series Multi-point
Lock
*IMPORTANT:
Pin 7 must be tied to ground in the access control panel.
Failure to follow proper ESD safe grounding procedures could lead to equipment failure
Lockbody
H N G
Power Supply
120 VAC
(By Others)
12/24VDC
Input
- +
READER NEG - Black, 1
READER POS - Red, 2
DATA 1 - White, 3
DATA 0 - Green, 4
RX (NO) - Orange, 5
RX (COM) - Blue, 6
*EARTH GROUND - Brown, 7
LED - Yellow, 8
Not Used
LOCK NEG - Violet, 9
LOCK POS - Gray, 10
DPS (NC) - Pink, 11
DPS (COM) - Tan, 12
7
SE LP10
Requires 12 or 24VDC
Electrical Access Control
Panel (By Others)
(-)
12/24VDC
(+)
DATA 1
DATA 0
RX (NC)
Use
Lock
RX (COM)
(NC) for
Relay
Fail Safe
Operation
DPS
DPS
(NO) Fail
Secure
Operation
.
FM456 08/20